NTU effectiveness calculator: rate a heat exchanger when the outlet temperatures are unknown

Enter the heat capacity rates, the conductance UA, the inlet temperatures and the flow arrangement of a heat exchanger to get the NTU, the effectiveness, the heat transferred and both outlet temperatures.

Updated on
Your inputs
Btu/h·°F

Value out of range

Btu/h·°F

Value out of range

Btu/h·°F

Value out of range

°F

Value out of range

°F

Value out of range

Results

Effectiveness ε

63.6 %

Heat capacity ratio Cr = Cmin / Cmax
0.80
Number of transfer units NTU = UA / Cmin
1.50
Heat transferred
610,819 Btu/h
Hot fluid outlet temperature
138.9 °F
Cold fluid outlet temperature
156.4 °F

The effectiveness-NTU method rates a heat exchanger from its UA, the capacity rates and the inlet temperatures, without iterating on the outlet temperatures. The NTU effectiveness calculator gives the capacity ratio, the NTU, the effectiveness, the heat transferred and the outlet temperatures for counterflow and parallel flow.

How the calculation works

  • Enter the heat capacity rate (mass flow × specific heat) of the hot and the cold fluids, the conductance UA of the exchanger (overall coefficient U × area A), and the two inlet temperatures.
  • Choose the flow arrangement: counterflow or parallel flow.
  • The calculator finds the capacity ratio Cr = Cmin / Cmax, the NTU = UA / Cmin and the effectiveness ε, the ratio of the real heat transfer to the maximum possible, Cmin × (Th,in − Tc,in).
  • For a counterflow exchanger, ε = [1 − e^(−NTU (1 − Cr))] / [1 − Cr e^(−NTU (1 − Cr))]. For parallel flow, ε = [1 − e^(−NTU (1 + Cr))] / (1 + Cr). Then it gives the heat transferred and the outlet temperatures.

Example

A counterflow exchanger has a hot stream of 10,000 Btu/h·°F entering at 200 °F and a cold stream of 8,000 Btu/h·°F entering at 80 °F, with UA = 12,000 Btu/h·°F. Cmin is 8,000, so Cr = 0.80 and NTU = 1.50. The effectiveness is (1 − e^−0.3) / (1 − 0.8 e^−0.3) = 63.6%. The heat transferred is 0.636 × 8,000 × 120 = 610,819 Btu/h. The hot fluid leaves at 138.9 °F and the cold fluid at 156.4 °F.

Why it matters

The calculator helps process, HVAC and mechanical engineers, plant operators and students to predict the performance of an existing heat exchanger, a recuperator, a coil or a radiator when the flows or the temperatures change, and to see the gain of a larger area. It is faster than the LMTD for rating problems.

Good to know

Use the true heat capacity rate: mass flow times specific heat at the average temperature. Check which stream has the smaller capacity rate, since it sets the maximum heat transfer. Take the clean UA reduced by a fouling factor. Compare the result with an energy balance on each stream to detect input errors.

The LMTD heat exchanger calculator sizes the area from the temperatures, the overall heat transfer coefficient calculator gives U, the heat recovery ventilator calculator applies the effectiveness to air and the specific heat calculator gives cp.

Frequently asked questions

When should the NTU method be used instead of the LMTD?

The LMTD method is easy when the four temperatures are known, to find the area. When the exchanger already exists and the outlet temperatures are not known, the LMTD equation needs an iteration. The effectiveness-NTU method avoids it: from UA, the capacity rates and the inlet temperatures, it gives the heat transfer and the outlet temperatures directly. It is the method of choice to rate an existing exchanger.

What is the effectiveness?

The effectiveness ε is the ratio of the actual heat transfer to the maximum that an infinitely long counterflow exchanger could achieve, which is Cmin (Th,in − Tc,in). It goes from 0 to 1, or 100%. A higher UA, which means a larger area or a better coefficient, raises the effectiveness, but with diminishing returns: the effectiveness of a counterflow exchanger with Cr = 1 is NTU / (1 + NTU).

Why is counterflow better than parallel flow?

In counterflow, the hottest hot fluid meets the hottest cold fluid at the cold end, so the temperature difference stays large and more heat is transferred for the same UA. The cold fluid can even leave hotter than the hot fluid does. In parallel flow, the two outlet temperatures approach each other, and the effectiveness is limited to 1 / (1 + Cr), which is 50% when Cr = 1.

What are the limits of this calculator?

It covers the two simple arrangements, counterflow and parallel flow, with constant fluid properties and no phase change. Shell-and-tube and cross-flow exchangers have other formulas. For a stream that boils or condenses, Cr is zero and ε = 1 − e^(−NTU). The calculator does not include the fouling, which lowers UA, or the heat losses to the environment.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.