Heat recovery ventilator calculator: effectiveness, heat recovered and saving

Enter the outdoor, indoor and supply air temperatures of a heat recovery ventilator, the airflow, the operating hours and the energy cost to get the effectiveness, the heat recovered, the remaining load and the annual saving.

Updated on
Your inputs
°F

Value out of range

°F

Value out of range

°F

Value out of range

CFM

Value out of range

h

Value out of range

$

Value out of range

Value out of range

Results

Heat recovered

5,832 Btu/h

Annual saving

$336.96

Apparent sensible effectiveness
72.0
Good heat recovery
Remaining heating load for the ventilation air
2,268 Btu/h
Annual heat recovered (therms)
233.3 therms

A heat recovery ventilator brings in fresh air while it keeps the heat of the exhaust air. The heat recovery ventilator calculator gives the effectiveness, the heat recovered, the remaining heating load of the ventilation air and the annual saving from the temperatures, the airflow and the cost of energy.

How the calculation works

  • Enter the outdoor temperature, the indoor (exhaust) temperature and the supply air temperature that you measure or read on the datasheet after the heat recovery ventilator.
  • Enter the airflow of the ventilation, the operating hours per year at that condition, the cost of fuel per therm and the efficiency of the heating system.
  • The calculator computes the apparent sensible effectiveness (Ts − To) / (Tr − To) and the heat recovered Q = 1.08 × CFM × (Ts − To).
  • It then gives the remaining load for the ventilation air, the energy recovered per year in therms and the annual saving in dollars.

Example

A heat recovery ventilator moves 150 CFM, with 20 °F outdoors and 70 °F indoors. The air is supplied at 56 °F. The effectiveness is (56 − 20) / (70 − 20) = 72%. The heat recovered is 1.08 × 150 × 36 = 5,832 Btu/h, and the remaining load to heat the air from 56 °F to 70 °F is 1.08 × 150 × 14 = 2,268 Btu/h. Over 4,000 hours, the energy recovered is 23.3 million Btu, or 233.3 therms. At $1.30 per therm and a 90% efficient furnace, the saving is $336.96 per year.

Why it matters

The calculator helps homeowners, builders, HVAC technicians and students to see what an HRV saves, to compare units with different effectiveness and airflow, and to estimate the payback of the equipment. It turns the numbers on the datasheet into the energy and money that matter.

Good to know

Use the effectiveness at the real flow rate, since it falls when the flow rises. Estimate the hours with the heating degree days of your climate. Remember that a ventilator is first for air quality, and the saving is a benefit that depends on the climate. Subtract the electricity of the fans for a net result.

The heat loss calculator gives the heating load of the building, the humidity ratio calculator covers the moisture of the air, the wall U-value calculator checks the insulation and the heating degree days calculator estimates the season.

Frequently asked questions

What is a heat recovery ventilator?

A heat recovery ventilator (HRV) brings in fresh air and exhausts stale air at the same time, through a heat exchanger where the two airstreams pass without mixing. The exhaust air warms the incoming air in winter, and cools it in summer. This keeps the indoor air healthy in a tight, well insulated house without the large energy loss of simply opening a window or running an exhaust fan.

How is the effectiveness defined?

The apparent sensible effectiveness is the temperature rise of the supply air divided by the maximum possible rise: (Ts − To) / (Tr − To). A value of 100% would mean that the supply air leaves at the indoor temperature. Good units reach 70% to 85% at the design flow. It is called apparent because it includes the effect of the fans, of the defrost cycles and of any leakage between the airstreams.

Why are the 1.08 and the savings only an estimate?

The constant 1.08 Btu/h per CFM and per °F applies to standard air. The saving also assumes a constant temperature difference during the hours of operation, while the real difference changes with the weather. For a precise result, use the hourly weather data or the degree-days. The fan power of the unit is also a cost that is not included here, and it can reduce the net saving.

What are the limits of this calculator?

It covers the sensible heat only. An energy recovery ventilator (ERV) also exchanges moisture, which gives a larger recovered energy in hot humid climates, and in dry cold ones it helps keep the indoor humidity up. The calculator does not include the defrost losses, the fan energy, the imbalance of the airflows, the cooling season or the cost of the unit.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.