Overall heat transfer coefficient calculator: add the resistances to find U

Enter the inside and outside film coefficients, the wall and the fouling factors to get the overall heat transfer coefficient U, the heat rate and the share of each thermal resistance.

Updated on
Your inputs
BTU/h·ft²·°F

Value out of range

BTU/h·ft²·°F

Value out of range

in

Value out of range

BTU/h·ft·°F

Value out of range

h·ft²·°F/BTU

Value out of range

h·ft²·°F/BTU

Value out of range

ft²

Value out of range

°F

Value out of range

Results

Overall heat transfer coefficient U

9.33 BTU/h·ft²·°F

Heat transfer rate
9,328 BTU/h
Share of resistance: inside film
4.7 %
Share of resistance: wall
0.2 %
Share of resistance: outside film
93.3 %
This resistance controls the heat transfer: improve it first
Share of resistance: fouling
1.9 %

Heat passing through a wall meets several resistances in series: the film on each side, the wall itself and any fouling. The overall heat transfer coefficient calculator adds them to find U. Enter the film coefficients, the wall and the fouling factors, plus the area and the temperature difference, to get U, the heat rate and the share of each resistance.

How the calculation works

  • Enter the film coefficients inside and outside the wall, the thickness and conductivity of the wall, the fouling factors on both sides, the area and the temperature difference.
  • The thermal resistances in series add up: 1/U = 1/hᵢ + Rfᵢ + t/k + Rfₒ + 1/hₒ (per unit area, for a plane wall).
  • The overall coefficient U is the inverse of the sum, and the heat is Q = U × A × ΔT.
  • The calculator shows the share of each resistance, so you can see which one controls the heat transfer.

Example

A steel tube wall (0.065 in, k = 26 BTU/h·ft·°F) has water inside (hᵢ = 200) and air outside (hₒ = 10 BTU/h·ft²·°F), with fouling of 0.001 h·ft²·°F/BTU on each side. The overall coefficient is U = 9.33 BTU/h·ft²·°F. With 20 ft² and 50 °F, the heat is 9,328 BTU/h. The outside film is 93.3 % of the total resistance, so a higher hₒ (fins, a fan) is the best improvement.

Why it matters

U is the first number needed in heat exchanger design, in boiler and condenser sizing, and in the analysis of an existing exchanger. The shares of the resistances show where the effort has the most effect, which is often on the gas side or on the fouling, not on the metal.

Good to know

The calculator uses the formula of a plane wall, which is a good approximation for thin tubes and for flat plates. For thick tubes, the areas inside and outside differ and the resistances must be referred to one surface with the log mean radius. The film coefficients must come from correlations or tests, and the fouling factors are typical design values, not measurements. Radiation can be included in the outside coefficient.

The LMTD calculator uses U to size a heat exchanger, the wall U-value calculator covers building walls with the same idea, the heat conduction calculator covers the wall resistance, and the fin efficiency calculator covers a way to improve a gas-side film.

Frequently asked questions

What is the overall heat transfer coefficient?

It is U, the single coefficient that relates the heat flow between two fluids separated by a wall to the temperature difference between them, Q = U A ΔT. It combines convection on both sides, conduction through the wall and any fouling layers. U is the main input of the LMTD and NTU methods of heat exchanger design.

Why do resistances add in series?

The same heat flow passes through each layer in turn, like current in resistors in series. Each layer has a thermal resistance per unit area: 1/h for a film, t/k for a wall and the fouling factor for a deposit. The total resistance is the sum, and U is its inverse. The layer with the largest resistance controls the result.

What is a fouling factor?

It is the thermal resistance of the layer of scale, rust, biological growth or deposit that builds up on a surface in use. TEMA gives typical values from 0.0001 to 0.001 m²·K/W (0.0005 to 0.005 h·ft²·°F/BTU). A heat exchanger is designed with a fouling allowance so that it still works at the end of its cleaning cycle.

How can U be improved?

By acting on the largest resistance. If it is a gas film, as in the example, add fins or raise the velocity. If it is fouling, clean the surface or choose a design that is easy to clean. A thinner or more conductive wall changes little in most cases, since metal walls have a small resistance.