Pipe insulation condensation calculator: is my chilled pipe insulation thick enough to stay dry?

Enter the pipe size, the insulation thickness and conductivity, the fluid and air temperatures and the humidity to get the dew point, the surface temperature, the margin above the dew point and the heat gain per foot.

Updated on
Your inputs
in

Value out of range

in

Value out of range

°F

Value out of range

°F

Value out of range

%

Value out of range

Btu·in/(h·ft²·°F)

Value out of range

Btu/(h·ft²·°F)

Value out of range

Results

Margin above the dew point

6.8 °F

No condensation: the surface stays above the dew point
Dew point of the air
69.3 °F
Surface temperature of the insulation
76.1 °F
Heat gain per foot of pipe
6.67 Btu/h per ft

The pipe insulation condensation calculator checks that the surface of an insulated cold pipe stays above the dew point of the air, from the pipe size, the thickness and the conductivity of the insulation, the fluid and air temperatures and the humidity, with the heat gain per foot.

How the calculation works

  • Enter the outside diameter of the pipe, the thickness and the conductivity of the insulation.
  • Enter the temperature of the fluid (for example chilled water), the air temperature and the relative humidity of the room.
  • Enter the outside film coefficient of the surface (about 1.5 Btu/h·ft²·°F in still air).
  • The calculator finds the dew point, the surface temperature of the insulation, the margin above the dew point and the heat gain per foot of pipe.

Example

A chilled water pipe of 2.375 in (2 in NPS) at 45 °F has 1 in of insulation of k = 0.25, in a room at 80 °F and 70% humidity. The dew point is 69.3 °F. The heat gain is 6.67 Btu/h per ft, and the surface of the insulation is at 76.1 °F, which gives a margin of 6.8 °F above the dew point. No condensation forms.

Why it matters

The calculator helps mechanical designers, insulation contractors, facility managers and energy auditors to check the thickness of the insulation of chilled water, refrigerant and cold domestic water lines, to see the effect of the humidity of the room and to estimate the heat gain. It avoids dripping pipes, damage and mold.

Good to know

Use the design humidity of the worst case, such as a mechanical room or an unconditioned attic in summer, and keep a margin of a few degrees. Seal the joints and the supports with a vapor barrier, and use a closed-cell insulation or a vapor retarder jacket. Inspect the insulation regularly, because a damaged one will let the moisture in.

The critical insulation radius calculator shows when insulation helps, the dew point calculator gives the dew point of the air, the insulation R-value calculator sizes the insulation of a wall and the moist air enthalpy calculator gives the properties of the air.

Frequently asked questions

Why does a cold pipe sweat?

When the surface of a pipe is colder than the dew point of the air around it, the water vapor of the air condenses on the surface. The water drips, wets the insulation and the ceilings, causes mold and corrodes the pipe. The insulation of a cold pipe is made to keep the outer surface above the dew point, and it is covered with a vapor retarder to stop the moist air from reaching the cold pipe.

How is the surface temperature found?

The heat flows from the room through the film of air and the insulation to the cold fluid. In steady state, the heat per unit length is q = 2π ΔT / (ln(r₂/r₁)/k + 1/(h r₂)), with r₁ the radius of the pipe and r₂ that of the insulation. The surface temperature is the air temperature minus q divided by the film conductance, 2π r₂ h. A thicker or a better insulation raises the surface temperature.

How is the dew point found?

The dew point is the temperature at which the air is saturated with its current water content. The calculator uses the Magnus formula from the air temperature and the relative humidity: for 80 °F (26.7 °C) and 70% it is 69.3 °F. A higher humidity, as in a mechanical room or in a hot and humid climate, raises the dew point and requires more insulation.

What are the limits of the calculator?

The calculator gives a steady state result for a horizontal pipe in still air, with a constant film coefficient. The real film coefficient depends on the air movement, the emissivity of the jacket and the orientation, and the vapor transmission through the insulation, the joints and the supports can cause condensation at a point even when the surface is above the dew point. The insulation specification of the project and the manufacturer govern.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.