Surface condensation risk calculator: will a cold surface get wet or moldy?

Enter the indoor temperature and humidity, the outdoor temperature and the U-factor of a wall, window or ceiling to get the inside surface temperature, the dew point, the margin and the relative humidity at the surface.

Updated on
Your inputs
°F

Value out of range

%

Value out of range

°F

Value out of range

Btu/h·ft²·°F

Value out of range

Results

Relative humidity at the surface

76.7 %

Low risk of condensation and mold
Inside surface temperature
51.6 °F
Dew point of the indoor air
44.6 °F
Margin above the dew point
7.1 °F
Temperature factor fRsi
0.694

A cold surface gets wet when it is below the dew point of the room air. The surface condensation risk calculator gives the inside surface temperature of a wall, a window or a ceiling, the dew point, the margin above it and the relative humidity at the surface, to check the risk of condensation and mold.

How the calculation works

  • Enter the indoor air temperature and the indoor relative humidity in the room that you want to check, such as a bathroom, a bedroom or a kitchen.
  • Enter the outdoor air temperature of the coldest design condition.
  • Enter the U-factor of the surface that you check: a window, a wall corner, a ceiling or a thermal bridge. A single glass window has about 1.0 and a good double glass window has about 0.3.
  • The calculator finds the inside surface temperature using the film resistance of 0.68 ft²·°F·h/Btu, the dew point of the air with the Magnus formula, and the relative humidity at the surface.

Example

A room is at 70 °F and 40% relative humidity, with 10 °F outside. The wall has a U-factor of 0.45. The surface temperature is 70 − 0.45 × 0.68 × 60 = 51.6 °F. The dew point of the room air is 44.6 °F, so the margin is 7.1 °F. The air next to the surface has a relative humidity of 76.7%, below the 80% threshold of mold growth. The temperature factor is (51.6 − 10) / 60 = 0.694.

Why it matters

The calculator helps homeowners, builders, inspectors and students to understand why a window drips or a corner grows mold, to check if an insulation upgrade is enough and to find the humidity that a room can accept in winter. It turns the U-factor and the room conditions into a clear risk figure.

Good to know

Check the coldest spot: a window frame, a corner, a thermal bridge. Keep the relative humidity of a room below 50% in cold weather. Ventilate bathrooms and kitchens, and do not block the air along the cold walls. If the surface humidity is above 80%, improve the insulation or lower the indoor humidity.

The dew point calculator gives the temperature of condensation, the wall U-value calculator gives the thermal transmittance, the humidity ratio calculator covers the moisture content of the air and the heat loss calculator estimates the heating load of the envelope.

Frequently asked questions

Why does condensation form on a surface?

Air can hold only so much water vapor, and the amount depends on the temperature. When the air touches a surface that is colder than its dew point, the air cools down to the saturation, and the water vapor condenses on the surface. This happens on cold windows, at the corners of walls, on thermal bridges and on uninsulated ducts and pipes, and it can lead to stains, rot and mold.

How is the surface temperature computed?

In steady state, the heat flow from the room air to the surface goes through a thin film of still air with a resistance Rsi, which is about 0.68 ft²·°F·h/Btu (0.12 to 0.13 m²·K/W) for walls. The drop of temperature in this film is U × Rsi × (Ti − To), so the surface temperature is Ts = Ti − U × Rsi × (Ti − To). A poorly insulated surface, with a high U, has a lower temperature.

What is the temperature factor fRsi?

The temperature factor is (Ts − To) / (Ti − To). It is 1 if the surface is at the indoor temperature and 0 if it is at the outdoor temperature. Building standards ask for a minimum value, often about 0.70 to 0.75, for the corners and the thermal bridges of housing, so that the humidity at the surface stays below the limit of mold growth, which is 80% relative humidity.

What are the limits of this calculator?

It uses a one-dimensional model and a constant surface resistance. The surface temperature in a corner or at a thermal bridge is lower than in the middle of the wall, so use the U-factor or the 2D result for the critical spot. A curtain, a piece of furniture or the lack of air movement increases the film resistance and lowers the temperature. The humidity indoors changes with the use and the ventilation.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.