Reinforced concrete column interaction diagram key points calculator

Enter the column size, the steel area, the materials and the factored load to get the pure axial capacity, the balanced point, the pure bending capacity and the type of control of the section.

Updated on
Your inputs
in

Value out of range

in

Value out of range

in

Value out of range

in²

Value out of range

ksi

Value out of range

ksi

Value out of range

kips

Value out of range

Results

Balanced axial load Pb

563 kips

Pure axial capacity P0
1,806 kips
Maximum design axial load φPn,max
939 kips
Balanced moment Mb
575 kip-ft
Pure bending capacity M0
315 kip-ft
Axial load ratio Pu / (φ Pb)
0.82
Below the balanced load: tension-controlled, ductile failure

The RC column interaction calculator gives the key points of the interaction diagram of a rectangular tied column: the pure axial capacity, the maximum design axial load, the balanced point and the pure bending capacity, with the type of control for your load.

How the calculation works

  • Enter the width and the depth of the column, the cover to the bar centers, the total steel area and the material strengths.
  • Enter the factored axial load to see on which side of the balanced point it falls.
  • The calculator gives the pure axial capacity, the maximum design axial load, the balanced point and the pure bending capacity, the key points of the interaction diagram.

Example

A column of 16 in × 20 in with 8 in² of steel, half on each face, d’ = 2.5 in, f’c = 5 ksi and Grade 60 steel has d = 17.5 in. The pure axial capacity is P0 = 0.85 × 5 × (320 − 8) + 60 × 8 = 1,806 kips, and the maximum design load is 0.65 × 0.8 × P0 = 939 kips. At the balanced point, c = 87 d / (87 + fy) = 10.36 in, so a = β1 c = 8.29 in. The compression steel has yielded, and Pb = 0.85 f’c b a = 563 kips with a moment of 575 kip-ft. In pure bending, the tension steel alone gives M0 = As fy (d − a / 2) = 315 kip-ft. A factored load of 300 kips is 0.82 of φPb, so the column is tension-controlled.

Why it matters

The calculator helps structural engineers, students and reviewers to check a column quickly, to see where a load falls compared with the balanced point and to understand why a column under a small load behaves like a beam. It is also a good check on the output of a design program.

Good to know

Check that the steel ratio is between 1 and 8 percent of the gross area. Use the total steel area, with half on each of the two faces parallel to the axis of bending. Compare the axial load with φPb to see whether the section is controlled by tension or by compression. For a load below the balanced point, adding steel increases the moment capacity a lot, but above it, a larger section or a stronger concrete helps more. Remember that a slender column needs a moment magnification.

The biaxial column calculator combines bending about both axes with Bresler’s equation, the RC beam flexural capacity calculator gives the pure bending of a beam, the rebar development length calculator gives the anchorage and the Euler buckling calculator gives the elastic buckling load of a slender column.

Frequently asked questions

What is an interaction diagram?

A short column can carry an axial load P and a moment M together, and the pairs of values that bring the section to failure form a curve, the interaction diagram. Points inside the curve are safe. The curve has a few key points: pure compression P0, the balanced point where the concrete reaches its crushing strain as the steel yields, and pure bending M0 with no axial load. The calculator gives these points.

What is the balanced point?

At the balanced point, the concrete reaches a strain of 0.003 at the same moment as the tension steel reaches yield. Below that axial load, the failure starts in the steel and is ductile. Above it, the concrete crushes first and the failure is sudden. The neutral axis depth is c = 87 d / (87 + fy) for fy in ksi. The calculator compares your load with φPb to tell you which case applies.

Why is there a maximum load of 0.80 P0?

No column is loaded exactly on its axis, so ACI 318 limits the nominal axial load of a tied column to 0.80 P0, which stands for a minimum eccentricity. With φ = 0.65, the maximum design load is 0.52 P0. The calculator shows it, since it flattens the top of the interaction diagram.

What does the calculator leave out?

The calculator takes a rectangular tied column with the steel placed equally on two faces, a short column, bending about one axis and a strength reduction factor of 0.65. It leaves out the intermediate bars, the slenderness effects, the biaxial bending, the transition of φ between tension and compression control and the displacement of the concrete by the compression steel. For a full diagram, use a section analysis program.

Was this calculator helpful?