The roof scupper sizing calculator gives the number of scuppers that a flat roof needs from its area, the design rainfall and the allowable depth of water, with the flow of one scupper by the weir equation.
How the calculation works
- Enter the roof area drained and the design rainfall intensity of your location, for the storm of the code (for example 4 in/h for a 100-year, 1-hour event in many regions).
- Enter the width of one scupper opening and the allowable depth of water above its invert, which is limited by the parapet and the structure.
- The calculator finds the design flow, the flow of one scupper by the weir equation, the number of scuppers and how heavily they are loaded.
Example
A roof of 10,000 ft² receives 4 in/h. The design flow is 0.0104 × 4 × 10,000 = 416 gpm. A scupper 12 in wide with 2 in of water above its invert passes Q = 3.0 × 1 × (2 / 12)^1.5 = 0.204 cfs, or 91.6 gpm. The roof needs 416 / 91.6 = 4.54, so 5 scuppers, which are loaded at 416 / (5 × 91.6) = 90.8%.
Why it matters
The calculator helps architects, roofing contractors, plumbing designers and building owners to check that a flat roof can drain a heavy storm, to size the overflow openings of a parapet and to see the effect of a wider scupper or of a deeper allowable depth. It avoids ponding, leaks and an overloaded roof structure.
Good to know
Place the scuppers at the low points of the roof and keep their invert at the level of the roof surface, not above it. Check the structure for the water that rises to the overflow level, and add a secondary scupper set higher than the main one. Keep the openings clean of leaves and debris, and follow the plumbing code for the rainfall intensity.
Related tools
The downspout calculator sizes the vertical drains, the rational method calculator gives the flow from a catchment, the rainwater calculator covers the harvest of the roof water and the Manning equation calculator sizes the pipes and the channels that receive the flow.