The sewer infiltration allowance calculator gives the length of the section, the allowable infiltration per day, the allowable infiltration per hour and the ratio of the measured infiltration to the allowable for a sanitary sewer, from the diameter, the length and the allowance of the specification.
How the calculation works
- Enter the diameter and the length of the sewer section.
- Choose the allowance given by the specification, in gallons per inch of diameter per mile per day.
- Enter the measured infiltration to get the allowable infiltration per day and per hour and the ratio of the measured to the allowable.
Example
A sewer of 8 in is 4,000 ft long, which is 4,000 / 5,280 = 0.758 mi. With an allowance of 200 gal/in/mi/day, the allowable infiltration is 200 × 8 × 0.758 = 1,212 gal/day, or 1,212 / 24 = 50.5 gal/h. A measured infiltration of 900 gal/day gives a ratio of 900 / 1,212 = 0.74, which is within the allowance.
Why it matters
The calculator helps sewer contractors, inspectors, utility engineers and students to prepare the acceptance test of a new sewer, to see if the measured infiltration is within the specification and to compare the effect of the diameter and the length.
Good to know
Read the allowance, the method and the duration of the test in the project specification, and test each section before the backfill is completed if the contract allows it. Check the joints and the manhole connections carefully during the installation, because most of the leaks are there. If the infiltration is over the limit, find the leak with a camera or a smoke test and repair it before retesting. Keep the test records with the as-built drawings, so that the owner can compare the rate of the infiltration in the years that follow.
Related tools
The Manning equation calculator relates the flow and the slope of the sewer, the pipe flow velocity calculator checks the velocity, the sewer line replacement cost calculator estimates the replacement and the wet well volume calculator sizes the pumping station.