Skip to content
Omnikalc

Thrust block size calculator: thrust at a pipe bend and the block area

Enter the pressure, the diameter and the bend angle of a pressure pipe and the bearing pressure of the soil to get the thrust force at the bend, the required bearing area of the concrete thrust block and its width.

Updated on
Your inputs
psi

Value out of range

in

Value out of range

°

Value out of range

psf

Value out of range

Value out of range

ft

Value out of range

Results

Thrust force at the bend

23,992 lb

Pipe cross-section area
113.1 in²
Required bearing area of the block
17.99 ft²
Required width of the block
6.00 ft

A pressure pipe pushes outward at every bend, and a thrust block holds it in place. The thrust block size calculator gives the thrust force at the bend from the pressure, the diameter and the angle, and the bearing area and the width of the concrete block needed against the soil.

How the calculation works

  • Enter the pressure of the pipe (the test pressure is often the governing case), its inside diameter and the deflection angle of the bend: 90° for an elbow, 45° or 22.5° for smaller bends, and 180° for a dead end or a cap.
  • Enter the allowable bearing pressure of the undisturbed soil against which the block will push, from the soil report, and a safety factor such as 1.5.
  • Enter the height of the block that you plan to cast against the trench wall.
  • The calculator finds the thrust T = 2 P A sin(θ/2), the bearing area T × SF / σ and the width of the block for that height.

Example

A 12 in pipe at 150 psi has a section of 113.1 in². At a 90° bend, the thrust is 2 × 150 × 113.1 × sin 45° = 23,992 lb. For a soil with a bearing pressure of 2,000 psf and a safety factor of 1.5, the bearing area is 23,992 × 1.5 / 2,000 = 18.0 ft². For a block of 3 ft of height, the width is 6.0 ft.

Why it matters

The calculator helps water and sewer contractors, utility designers, plumbers and students to size the thrust blocks of a pressure main and to see why the test pressure and the bend angle matter. It gives a first size to compare with the standard details of the utility.

Good to know

Use the test pressure, which is often 1.5 times the working pressure, for the thrust. Cast the block against undisturbed soil and keep the joints of the fitting free of concrete. If the soil is weak, use a larger block, restrained joints or both. Check the local standard details of the water utility.

The pipe flow velocity calculator checks the speed in the pipe, the hydrostatic pressure calculator gives the static pressure, the bearing capacity calculator covers the strength of the soil and the footing size calculator sizes concrete footings.

Frequently asked questions

What is a thrust block?

A pressure pipe pushes outward at every bend, tee, valve, reducer or dead end, since the pressure acts on a surface that is not balanced by the pipe. If the joints are not restrained, this thrust can pull the pipe apart. A thrust block is a mass of concrete cast between the fitting and the undisturbed soil of the trench wall, which spreads the thrust over a large area of soil.

How is the thrust computed?

At a bend of angle θ, the thrust on the fitting is T = 2 P A sin(θ/2), where P is the pressure and A is the inside area of the pipe. For a dead end or a cap, θ is 180° and T = P A. At a tee, the thrust is P A of the branch. Use the highest pressure that the line will see, which is often the test pressure and may include a surge allowance.

How is the block sized?

The block must give a bearing area A = T × SF / σ against the soil, where σ is the allowable bearing pressure of the soil. The pressure of the thrust is then spread on the soil. The block must also be cast against undisturbed soil, not against backfill, and its center of pressure should be in line with the fitting. The safety factor is commonly 1.5 for soil bearing.

What are the limits of this calculator?

It sizes a horizontal bearing block only. Vertical bends and the thrust of a pipe that goes up or down need a block that resists by weight and anchors. The calculator does not include the friction of the pipe, the unbalanced force of a surge, the restraint of the joints, which is an alternative to blocks, or the water table. Follow the guide of the pipe manufacturer and the design of the engineer.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.