Boiler blowdown calculator: blowdown rate, makeup flow and energy cost

Enter the steam output, the TDS of the feedwater and the TDS limit of the boiler to get the cycles of concentration, the blowdown rate, the makeup water flow, the heat lost and the annual fuel cost of the blowdown.

Updated on
Your inputs
lb/h

Value out of range

ppm

Value out of range

ppm

Value out of range

°F

Value out of range

°F

Value out of range

h

Value out of range

$

Value out of range

Value out of range

Results

Blowdown rate

7.14 % of steam

Low blowdown: efficient water use
Cycles of concentration
15.0
Blowdown flow
714.3 lb/h
Makeup water flow
10,714 lb/h
Heat lost with the blowdown
98,571 Btu/h
Annual fuel cost of the blowdown
$12,814

A boiler must drain a part of its water to keep the dissolved solids under the limit. The boiler blowdown calculator gives the cycles of concentration, the blowdown rate, the makeup water, the heat lost with the blowdown and its annual fuel cost from the steam output and the TDS of the feedwater and of the boiler.

How the calculation works

  • Enter the steam output of the boiler, and the dissolved solids (TDS) of the feedwater and the maximum TDS that the boiler water may have, from the maker’s limit or the water treatment company.
  • Enter the temperature of the boiler water (the saturation temperature at the operating pressure, 338 °F at 100 psig) and the temperature of the makeup water.
  • Enter the operating hours per year, the cost of fuel and the efficiency of the boiler.
  • The calculator finds the cycles of concentration, the blowdown rate = steam × F / (B − F), the makeup flow, the heat lost with the hot blowdown water and its yearly cost.

Example

A boiler makes 10,000 lb/h of steam, with 200 ppm of solids in the feedwater and a limit of 3,000 ppm in the boiler. The cycles of concentration are 3,000 / 200 = 15. The blowdown is 10,000 × 200 / (3,000 − 200) = 714 lb/h, or 7.14% of the steam, and the makeup water is 10,714 lb/h. The blowdown water at 338 °F replaces water at 200 °F, so the heat lost is 714 × 138 = 98,571 Btu/h. Over 8,000 hours, at $1.30 per therm and 80% efficiency, it costs $12,814 a year.

Why it matters

The calculator helps plant operators, energy managers, water treatment technicians and students to see what the blowdown costs, to compare the effect of better makeup water and to justify a heat recovery or an automatic control. It turns the water chemistry into fuel and money.

Good to know

Use the TDS limit given by the maker for your pressure, and measure the real TDS of the feedwater, which includes the returned condensate. Check that the blowdown is not too low, since scale costs more than the blowdown. Install an automatic control and a heat recovery system if the blowdown is above 5% of the steam.

The boiler size calculator sizes the boiler, the water conductivity and TDS calculator converts between conductivity and solids, the heat of combustion calculator gives the energy of the fuel and the specific heat calculator covers the heat content of water.

Frequently asked questions

What is boiler blowdown?

When a boiler makes steam, the dissolved solids of the feedwater stay in the boiler water and become more concentrated. If they get too high, they form scale, foam, and carry-over of water into the steam. To control this, a part of the boiler water is drained, which is the blowdown, and replaced by makeup water with a lower concentration. The blowdown can be continuous, from the surface, or intermittent, from the bottom of the boiler to remove sludge.

How is the blowdown rate computed?

The solids that enter with the feedwater must leave with the blowdown. With a steam flow S, a blowdown flow B′, a feedwater concentration F and a boiler concentration B, the balance of the solids gives (S + B′) × F = B′ × B, so B′ = S × F / (B − F). The cycles of concentration are B / F: the more cycles, the less water is blown down. Better treatment of the makeup water, such as softening or reverse osmosis, allows more cycles.

How can the blowdown loss be reduced?

Reduce the solids of the feedwater with better makeup water treatment and more condensate return. Use an automatic continuous blowdown control based on the conductivity, which keeps the TDS close to the limit and avoids a blowdown that is larger than needed. Add a heat exchanger or a flash tank to recover the heat of the blowdown to preheat the makeup water. These measures often pay back in less than two years.

What are the limits of this calculator?

It assumes a steady operation, a constant feedwater quality and a heat loss that is the sensible heat of the water between the boiler and the makeup temperatures, with a specific heat of 1 Btu/lb·°F. It does not include the flash steam, the intermittent bottom blowdown, the cost of the water and the chemicals or the heat recovered. The maximum TDS depends on the boiler pressure and on the maker’s recommendation.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.