Cooling tower performance calculator: range, approach, effectiveness, blowdown and makeup

Enter the water flow, the hot and cold water temperatures, the wet-bulb temperature and the cycles of concentration to get the range, the approach, the heat rejected, the evaporation, the blowdown and the makeup water.

Updated on
Your inputs
gpm

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

Value out of range

Results

Heat rejected

417 tons

Range
10.0 °F
Approach to the wet-bulb temperature
7.0 °F
Normal approach
Tower effectiveness
58.8 %
Evaporation loss
10.00 gpm
Blowdown
3.33 gpm
Makeup water needed
13.33 gpm

A cooling tower removes heat from water by evaporation. The cooling tower calculator gives the range, the approach, the effectiveness and the heat rejected from the flow and the temperatures, and the evaporation, the blowdown and the makeup water for a chosen number of cycles of concentration.

How the calculation works

  • Enter the circulating water flow, the hot water temperature entering the tower and the cold water temperature leaving it.
  • Enter the wet-bulb temperature of the entering air and the cycles of concentration of the water treatment.
  • The calculator gives the range (hot − cold), the approach (cold − wet bulb) and the effectiveness range / (range + approach).
  • It also gives the heat rejected, the evaporation loss (about 0.1 % of the flow per °F of range), the blowdown and the makeup water.

Example

A cooling tower handles 1,000 gpm, receives water at 95 °F and returns it at 85 °F, with an air wet-bulb of 78 °F. The range is 10 °F and the approach is 7 °F, so the effectiveness is 10 / 17 = 58.8 %. The heat rejected is 500 × 1,000 × 10 / 12,000 = 417 tons. The evaporation is 0.001 × 1,000 × 10 = 10 gpm. At 4 cycles, the blowdown is 10 / 3 = 3.33 gpm and the makeup is 13.33 gpm.

Why it matters

The calculator helps facility managers, HVAC engineers, water treatment technicians and students to check the performance of a tower, to estimate its water use and to see the effect of the cycles of concentration on the makeup and the cost. It also helps to compare the performance in different weather conditions.

Good to know

The calculator uses simple rules for the evaporation (about 0.1 % of the flow per 10 °F of range) and ignores the drift loss, the effect of the humidity on the rule and the heat added by the fan. The capacity of a real tower is given by the manufacturer’s curves for the flow, the range, the approach and the wet-bulb temperature. Check also the local rules for water treatment and for the control of legionella.

The heat exchanger LMTD calculator covers other exchangers, the wet-bulb temperature calculator finds the wet bulb from the weather, the dew point calculator gives the dew point of the air, and the pump power calculator gives the energy of the circulating pump.

Frequently asked questions

What are the range and the approach of a cooling tower?

The range is the difference between the temperature of the hot water entering the tower and that of the cold water leaving it. It shows how much heat the tower removes for the given flow. The approach is the difference between the cold water temperature and the wet-bulb temperature of the entering air. The wet-bulb temperature is the lowest temperature that the water can reach by evaporation, so the approach shows how close the tower comes to this limit.

What is the tower effectiveness?

The effectiveness of a cooling tower is the range divided by the sum of the range and the approach, that is the ratio of the real cooling to the largest cooling possible down to the wet-bulb temperature. A typical tower has an effectiveness of 50 % to 70 %. A smaller approach increases the effectiveness but needs a larger tower, more fill and more fan power, and the cost rises quickly under an approach of 5 °F.

How is the evaporation loss estimated?

A common rule is that the evaporation is about 0.1 % of the circulating flow for each 10 °F (5.6 °C) of range, which gives 0.001 × flow × range in °F, or 0.0018 × flow × range in °C. This comes from the latent heat of vaporization of water. The calculation ignores the drift losses, which are small in a modern tower, and the variation with the humidity and the temperature.

What are cycles of concentration and blowdown?

As water evaporates, the dissolved minerals stay behind and their concentration increases. The cycles of concentration are the ratio of the concentration in the circulating water to that in the makeup water. To limit the scaling and the corrosion, a part of the water is drained as blowdown. Blowdown equals the evaporation divided by (cycles − 1), and the makeup water is the sum of the evaporation and the blowdown.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.