Enter the current, the wire length, size and material and the time to get the resistance, the heat power and the temperature rise if no heat escapes.

Updated on
Your inputs
A

Value out of range

ft

Value out of range

s

Value out of range

Results

Heat power in the wire

50.5 W

Resistance of the wire
0.1263 Ω
Heat power per foot
1.01 W/ft
Temperature rise if no heat escapes
49.9 °F
Energy turned into heat
0.842 Wh

Every wire that carries current warms up, and a wire that is too small for its current can get hot enough to melt its insulation. The Joule heating calculator takes the current, the length, the size and the material of the wire and the time, and gives its resistance, the heat power, the heat per foot, the temperature rise if no heat escapes and the energy turned into heat.

How the calculation works

  • Enter the current in amperes, the length of the wire and its size in AWG, and pick the material.
  • Enter the time that the current flows.
  • The calculator finds the resistance from the resistivity, the length and the cross-section, then the heat power with P = I² × R.
  • It also finds the mass of the wire and the temperature rise with ΔT = P × t / (m × c), which is the worst case, since it assumes that no heat leaves the wire.

Example

A 50 ft length of 14 AWG copper wire (2.081 mm²) carries 20 A for 60 s. The resistance is 0.01724 × 15.24 / 2.081 = 0.1263 Ω, so the heat power is 20² × 0.1263 = 50.5 W, or 1.01 W per foot. The wire weighs 0.284 kg, so if no heat escaped, it would warm by about 27.7 °C, or 49.9 °F, in the minute. The energy turned into heat is 0.84 Wh.

Why it matters

The same I²R heat explains why long, thin wires waste power, why fuses blow, why extension cords warm up and how heating elements work. A quick calculation helps with checking a cord, sizing a heating wire or understanding a loss in a circuit, before you wire it up.

Good to know

The calculator uses fixed values of the resistivity, the density and the specific heat at room temperature. The resistance of metals rises with temperature, which raises the heat, and the real wire also loses heat by convection and radiation. It gives the heating of a straight wire in a short time and no more. Follow the electrical code for wiring.

The wire resistance calculator gives the resistance of any wire, the wire ampacity calculator gives the safe current, the Ohm’s law calculator relates voltage, current and resistance, and the heating power calculator sizes heaters.

Frequently asked questions

What is Joule heating?

It is the heat produced when an electric current flows through a resistance. The power is the current squared times the resistance, P = I²R, and it does not depend on the direction of the current. It is the basis of heaters, toasters and fuses, and it is the loss in power lines and wiring.

Why does the current matter so much?

Because the heat grows with the square of the current. Doubling the current makes four times the heat in the same wire. This is why an overloaded circuit can overheat quickly, and why ampacity tables limit the current for each wire size, with a margin for the insulation.

Why is the temperature rise only an upper bound?

The calculation is adiabatic: it assumes that all the heat stays in the wire. In practice, the wire loses heat to the air and to the insulation, and it settles at a lower temperature where the loss equals the heating. It is a good estimate for short pulses such as a fault current or a fuse.

How do I choose a heating wire?

A heating element needs a high resistivity and a high melting point so that a short length makes enough heat, which is why nichrome is used. With the same current and size, a nichrome wire makes about 64 times the heat of a copper wire. For real heaters, follow the manufacturer's data and the electrical code.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.