Skip to content
Omnikalc

Cable pulling tension and sidewall pressure calculator for a conduit

Enter the weight of the cables, the lengths, the friction, the bend angle and radius and the allowable limits to get the pulling tensions, the sidewall pressure and the ratio to the allowable.

Updated on
Your inputs
lb/ft

Value out of range

ft

Value out of range

ft

Value out of range

Value out of range

°

Value out of range

in

Value out of range

lb

Value out of range

lb/ft

Value out of range

Results

Highest ratio to the allowable

0.18

The pull is within the limits of the cable and of the bend
Tension before the bend
157.5 lb
Tension after the bend
272.9 lb
Tension at the end of the pull
377.9 lb
Sidewall pressure in the bend
91.0 lb/ft

The cable pulling tension and sidewall pressure calculator gives the tension before the bend, the tension after the bend, the tension at the end of the pull, the sidewall pressure and the highest ratio to the allowable for cables pulled in a conduit, from the weight of the cables, the friction and the geometry of the run.

How the calculation works

  • Enter the weight of the cables, the lengths before and after the bend and the coefficient of friction.
  • Enter the angle and the radius of the bend, and the allowable tension and sidewall pressure of the cables.
  • The calculator finds the tension along the pull, the sidewall pressure in the bend and the highest ratio to the limits.

Example

Cables of 3 lb/ft are pulled 150 ft in a straight conduit with a friction of 0.35, which gives a tension of 3 × 0.35 × 150 = 157.5 lb. A 90 degree bend multiplies it by e^(0.35 × 1.571) = 1.73, so the tension after the bend is 272.9 lb, and 377.9 lb after 100 ft more. With a radius of 36 in, the sidewall pressure is 272.9 / 3 = 91.0 lb/ft. The highest ratio is 0.18 of the allowable.

Why it matters

The calculator helps electrical contractors, foremen, designers and students to check a cable pull before the work, to decide where to put a pull box, and to see how the friction, the length and the radius of the bends change the tension and the pressure on the cable.

Good to know

Use a wire-pulling lubricant that suits the cable jacket, and apply it all along the pull. Keep the pulling speed steady, use a tension meter on a long pull, and pull the cable from the side where the tension is lowest. Remove the sharp edges and burrs at the ends of the conduit, and use a pulling eye that is rated for the pull.

The wire ampacity calculator gives the current capacity of a conductor, the wire size and voltage drop calculator gives the size for a long run, the conduit fill calculator checks the fill and the cable tray fill calculator checks a cable tray.

Frequently asked questions

How is the pulling tension calculated?

For a straight horizontal run, the tension is the weight of the cables per unit of length times the coefficient of friction times the length. At a bend, the tension is multiplied by e raised to the coefficient of friction times the angle of the bend in radians, which is the capstan equation. The tension after the bend is the new starting tension for the next straight section.

What is the sidewall pressure?

The sidewall pressure is the force by which the cable is pressed against the inside of the conduit at a bend. For one cable, it is the tension at the exit of the bend divided by the radius of the bend. A high pressure crushes the insulation and damages the cable. The limit depends on the cable, and a value of about 500 lb/ft (7,300 N/m) is often used for the usual power cables.

How can the tension be reduced?

A lubricant lowers the coefficient of friction, often from 0.5 to 0.2 or less. A larger radius of the bend reduces the sidewall pressure, and fewer bends lower the tension. It is better to pull the cables in the direction in which the bends are near the beginning of the pull, to use pull boxes in a long run and to pull with a smooth speed without jerks.

What are the limits of the calculator?

The calculator treats a horizontal run with one bend and a constant coefficient of friction. It does not take into account the vertical runs, the several bends, the jam of the cables in a bend, the effect of the cradle of three cables, the temperature or the type of the lubricant. The allowable tension must come from the data of the manufacturer of the cable.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.