Silo wall pressure by Janssen and hoop tension calculator

Enter the silo diameter, the depth of the material, its unit weight, the lateral pressure ratio and the wall friction to get the pressures, the hoop tension and the wall friction load.

Updated on
Your inputs
ft

Value out of range

ft

Value out of range

pcf

Value out of range

Value out of range

Value out of range

Results

Horizontal pressure on the wall

584 psf

Hydraulic radius
6.00 ft
Vertical pressure at the depth
1,167 psf
Hoop tension per foot of height
7,004 lb/ft
Weight of the stored material
1,221 kips
Weight carried by the wall friction
693 kips
Share carried by the wall friction
56.8 %

The silo Janssen pressure calculator gives the vertical and horizontal pressures on the wall of a silo, the hoop tension per foot of height and the weight carried by the wall friction.

How the calculation works

  • Enter the diameter of the silo and the depth of the stored material.
  • Enter the bulk unit weight of the material, the lateral pressure ratio and the wall friction coefficient.
  • The calculator gives the vertical and horizontal pressures by the Janssen equation, the hoop tension and the weight carried by the wall.

Example

A silo 24 ft in diameter holds 60 ft of corn weighing 45 pcf, with K = 0.5 and a wall friction coefficient of 0.4. The hydraulic radius is R = D / 4 = 6.00 ft. The Janssen vertical pressure at the bottom is γ R / (μ K) × (1 − e^(−μ K z / R)) = 1,167 psf, much less than the 2,700 psf of the full column. The horizontal pressure is 584 psf and the hoop tension is 7,004 lb/ft. The stored material weighs 1,221 kips, and the wall friction carries 693 kips, or 56.8 % of it.

Why it matters

The calculator helps agricultural, industrial and structural engineers, silo operators and students to see how the pressure of a stored material builds up with depth, to estimate the hoop tension for the wall and to compare the load on the floor with the weight of the contents.

Good to know

Run the calculator with the smallest and the largest values of K and of the wall friction given for the material, and use the more severe result for each check. Apply the overpressure factors of your design standard for the discharge, and do not use the static value alone. Check the wall for the vertical friction load and the buckling, and the foundation for the load that the wall carries.

The hopper outlet arching calculator gives the outlet size that prevents arching, the grain bin calculator gives the capacity of a bin, the bucket elevator calculator sizes a conveying elevator and the stockpile volume calculator gives the tonnage of a pile.

Frequently asked questions

What is the Janssen equation?

In a deep silo, part of the weight of the stored material is carried by the friction on the wall, so the vertical pressure does not grow without limit like the pressure of a liquid. Janssen showed that the vertical pressure at depth z is pv = γ R / (μ K) × (1 − e^(−μ K z / R)), where R is the hydraulic radius, equal to the area divided by the perimeter, or D / 4 for a circular silo. The pressure tends toward a maximum value with depth.

How is the wall pressure found?

The horizontal pressure on the wall is the lateral pressure ratio K times the vertical pressure, ph = K pv. For a circular silo, a ring of 1 ft of height has a hoop tension T = ph D / 2, which the wall reinforcement or the steel plate and the bolts must carry. The friction on the wall is μ ph, and it is integrated over the wall to give the vertical load on the wall and its foundation.

Where do K and the friction come from?

The ratio K and the wall friction coefficient depend on the material, its moisture, the roughness of the wall and the direction of the flow. Standards give values for common materials such as grain, cement and coal, with a range for each. Use the combination that gives the larger value for the effect you check: a low friction and a high K for the wall pressure, and a high friction for the load on the wall.

What does the calculator leave out?

The Janssen equation is for the static state of a filled silo. During discharge, the pressures on the wall can be much higher and uneven, so the design standards apply an overpressure factor to the static pressure, and they add the effect of the eccentric discharge and the thermal loads. The calculator also leaves out the pressure in the hopper, the dynamic effects and the buckling of the wall. It is a first estimate and not a design to a standard.