The cable short-circuit withstand calculator gives the minimum conductor size for a fault current and clearing time, the margin of the cable you chose, its withstand time and its withstand current.
How the calculation works
- Enter the short-circuit current, the clearing time of the protection and the initial and final temperatures of the conductor.
- Choose the conductor material and enter the size of the conductor.
- The calculator gives the minimum size, the margin, the withstand time and the withstand current.
Example
A copper cable with insulation rated for 90 °C and 250 °C in a short circuit sees 22,000 A for 0.5 s. The minimum size is A = I √t / √(0.0297 log10((T2 + 234) / (T1 + 234))) = 216.2 kcmil. A 250 kcmil cable is 1.16 times the minimum size. It can withstand the fault for 0.67 s, or 25.4 kA for 0.5 s.
Why it matters
The calculator helps electrical engineers, designers, electricians and students to check that a cable is not damaged by a short circuit before the protection clears it, and to see how the clearing time and the fault current change the size needed.
Good to know
Use the maximum fault current at the cable and the longest clearing time of the protection, including the delay of a selective trip. A faster protection device allows a smaller cable, so check the time-current curve. Use the temperature limits of the insulation of your cable, and check the grounding conductor and the shield with the same method. Remember that the fault current can rise when the utility upgrades its system or when a transformer is replaced, so keep the margin and review the calculation after any change of the source.
Related tools
The wire size voltage drop calculator sizes a conductor for the drop, the wire ampacity calculator gives the current rating, the transformer fault current calculator gives the available fault current and the arc flash incident energy calculator estimates the energy of an arc.