Cable short-circuit withstand and minimum conductor size calculator

Enter the fault current, the clearing time, the temperatures, the material and the conductor size to get the minimum size, the margin and the withstand time of the cable.

Updated on
Your inputs
A

Value out of range

s

Value out of range

°C

Value out of range

°C

Value out of range

kcmil

Value out of range

Results

Conductor size to the minimum size

1.16

The conductor withstands the fault
Minimum conductor size for the fault
216.2 kcmil
Time the conductor can withstand the current
0.67 s
Current the conductor can withstand for the clearing time
25.44 kA

The cable short-circuit withstand calculator gives the minimum conductor size for a fault current and clearing time, the margin of the cable you chose, its withstand time and its withstand current.

How the calculation works

  • Enter the short-circuit current, the clearing time of the protection and the initial and final temperatures of the conductor.
  • Choose the conductor material and enter the size of the conductor.
  • The calculator gives the minimum size, the margin, the withstand time and the withstand current.

Example

A copper cable with insulation rated for 90 °C and 250 °C in a short circuit sees 22,000 A for 0.5 s. The minimum size is A = I √t / √(0.0297 log10((T2 + 234) / (T1 + 234))) = 216.2 kcmil. A 250 kcmil cable is 1.16 times the minimum size. It can withstand the fault for 0.67 s, or 25.4 kA for 0.5 s.

Why it matters

The calculator helps electrical engineers, designers, electricians and students to check that a cable is not damaged by a short circuit before the protection clears it, and to see how the clearing time and the fault current change the size needed.

Good to know

Use the maximum fault current at the cable and the longest clearing time of the protection, including the delay of a selective trip. A faster protection device allows a smaller cable, so check the time-current curve. Use the temperature limits of the insulation of your cable, and check the grounding conductor and the shield with the same method. Remember that the fault current can rise when the utility upgrades its system or when a transformer is replaced, so keep the margin and review the calculation after any change of the source.

The wire size voltage drop calculator sizes a conductor for the drop, the wire ampacity calculator gives the current rating, the transformer fault current calculator gives the available fault current and the arc flash incident energy calculator estimates the energy of an arc.

Frequently asked questions

Why does a cable have a short-circuit rating?

In a short circuit, the current is many times the normal current and it heats the conductor in a fraction of a second, too fast for the heat to escape. If the conductor gets too hot, the insulation is damaged, and the cable can fail at the next fault. The size of the conductor and the time that the protection takes to clear the fault must be such that the final temperature stays below the limit of the insulation.

What is the formula?

For copper, the adiabatic equation of the ICEA standard is (I / A)² t = 0.0297 log10((T2 + 234) / (T1 + 234)), with I in amperes, A in circular mils, t in seconds, T1 the temperature before the fault and T2 the final temperature. For aluminum the constants are 0.0125 and 228. The calculator solves it for the minimum area, for the withstand time and for the withstand current. In SI units, the equation is S = I √t / k.

What temperatures should I use?

The temperature before the fault is the maximum operating temperature of the conductor, often 90 °C for XLPE and 75 °C for some PVC and THW insulations. The final temperature is the short-circuit limit of the insulation, about 250 °C for XLPE and EPR and 150 to 160 °C for PVC. Use the values of the cable data sheet, and the fault current and clearing time at the location of the cable.

What does the calculator leave out?

The calculation is adiabatic, so it applies to faults shorter than about 5 seconds, and it leaves out the heat that flows to the insulation and the surroundings, which gives a margin for faults of longer duration. It also leaves out the shield or the sheath of the cable, the mechanical forces between conductors, the connectors and the terminations. Check the cable, the protective device curve and the breaker settings together, using the standard of your project.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.