Combustion air opening sizing calculator: how big must the combustion air openings be?

Enter the total input of the gas appliances and the volume of the space to get the volume needed, the confined space ratio and the free area of the openings for indoor air, one outdoor opening and two outdoor openings.

Updated on
Your inputs
Btu/h

Value out of range

ft³

Value out of range

Results

Each of two openings, air from inside the building

140 in²

Volume needed to be unconfined
7,000 ft³
Volume of the space over the volume needed
0.21
The space is confined: openings for combustion air are required
One opening to the outdoors (1 in² per 3,000 Btu/h)
47 in²
Each of two openings to the outdoors (1 in² per 4,000 Btu/h)
35 in²

The combustion air opening sizing calculator tells whether a space is confined from the total input of the gas appliances and the volume of the space, and gives the free area of the openings for the air taken from inside the building or from the outdoors, following the International Fuel Gas Code.

How the calculation works

  • Enter the total input of all the fuel-burning appliances in the space, in Btu/h, for example a furnace and a water heater.
  • Enter the volume of the room or space where they are installed.
  • The calculator compares the volume with the 50 ft³ per 1,000 Btu/h of the International Fuel Gas Code to tell whether the space is confined, and gives the free area of the openings for the three usual methods.

Example

A furnace of 100,000 Btu/h and a water heater of 40,000 Btu/h make a total input of 140,000 Btu/h in a space of 1,500 ft³. The volume needed to be unconfined is 50 × 140 = 7,000 ft³, so the space is only 0.21 of it, and it is confined. With indoor air, two openings of 140 in² each are required (1 in² per 1,000 Btu/h, with a minimum of 100 in²). To the outdoors, one opening needs 46.7 in², or two openings 35 in² each.

Why it matters

The calculator helps heating contractors, home inspectors, builders and homeowners to check the combustion air of a furnace, a boiler or a water heater in a closet or a small room, to size the vents and to see why a tight space is a hazard. It helps to avoid carbon monoxide and poor combustion.

Good to know

Add the input of all the appliances in the same space. Place the openings high and low, and do not close them with a door or a cover. Account for the free area of the louvers and screens, which is often only 25 to 75% of the gross area. Keep exhaust fans and dryers from depressurizing the space, and install a carbon monoxide alarm.

The combustion efficiency calculator gives the stack loss, the chimney height calculator sets the height of the flue, the boiler size calculator sizes a boiler and the gas pipe sizing calculator checks the capacity of the gas line.

Frequently asked questions

What is combustion air?

Fuel-burning appliances such as furnaces, boilers and water heaters need air for the combustion, about 10 ft³ of air per cubic foot of natural gas, plus the air that is drawn up the flue by the draft. In a tight building this air must be supplied on purpose, otherwise the appliance burns badly, makes carbon monoxide and can backdraft, which is dangerous. The codes set the minimum size of the openings for this air.

What is a confined space?

The International Fuel Gas Code calls a space confined when its volume is less than 50 ft³ for each 1,000 Btu/h of the total input of the appliances. A space that is not confined can take the air from the infiltration of the building, if the building is not very tight. A confined space, such as a closet or a small mechanical room, needs openings for the air from the other spaces or from the outdoors.

How are the openings sized?

For the air from inside the building, two permanent openings are required, one within 12 in of the ceiling and one within 12 in of the floor, each with a free area of 1 in² per 1,000 Btu/h and at least 100 in². For the air from the outdoors, two openings of 1 in² per 4,000 Btu/h if they are directly to the outside or through vertical ducts, or one opening of 1 in² per 3,000 Btu/h within 12 in of the top. Louvers and screens reduce the free area.

What are the limits of the calculator?

The calculator applies the standard method of the fuel gas code. Other methods exist, such as combustion air ducts of different lengths, direct vent and sealed combustion appliances, which do not need the openings, and mechanical supply. The local code, the manufacturer’s instructions and a combustion safety test on a tight house govern. A qualified heating contractor should check the installation.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.