Skip to content
Omnikalc

Combustion efficiency calculator: stack loss and excess air from flue gas readings

Enter the fuel, the oxygen in the flue gas and the flue gas and air temperatures to get the excess air, the stack loss and the combustion efficiency of a boiler, a furnace or a water heater.

Updated on
Your inputs
%

Value out of range

°F

Value out of range

°F

Value out of range

Results

Combustion efficiency (Siegert)

92.6 %

Efficient combustion
Excess air
23.5 %
Normal range of excess air
Stack loss
7.44 %
Efficiency gain at 3% oxygen
0.34 points

The flue gas tells how well a burner works. The combustion efficiency calculator uses the oxygen and the temperature of the flue gas to find the excess air, the stack loss and the combustion efficiency with the Siegert formula, for natural gas, heating oil or propane.

How the calculation works

  • Select the fuel: natural gas, heating oil or propane. Each fuel has its own constants in the Siegert formula.
  • Enter the oxygen measured in the flue gas with a combustion analyzer (dry basis) and the flue gas temperature, measured in the stack before any dilution.
  • Enter the combustion air temperature, usually the temperature of the boiler room.
  • The calculator gives the excess air O₂ / (21 − O₂), the stack loss and the combustion efficiency from the Siegert formula, and the gain that you would get by trimming the oxygen to 3%.

Example

A gas boiler shows 4.0% oxygen, a flue gas temperature of 350 °F and a combustion air temperature of 70 °F. The difference is 280 °F, or 155.6 K. The excess air is 4.0 / (21 − 4.0) = 23.5%. With the constants A2 = 0.66 and B = 0.009 for natural gas, the stack loss is 155.6 × (0.66 / 17 + 0.009) = 7.44%. The combustion efficiency is 100 − 7.44 = 92.6%. Trimming the oxygen to 3% would reduce the loss by 0.34 points.

Why it matters

The calculator helps heating technicians, energy auditors, homeowners and students to read a combustion analysis, to see how much a burner adjustment can save and to compare the readings before and after a tune-up. It turns two numbers of the analyzer into a clear efficiency.

Good to know

Measure after the appliance has run for several minutes, with the probe in the center of the flue. Keep the oxygen high enough to avoid carbon monoxide. A flue gas temperature that is much higher than usual shows dirty heat exchange surfaces. Do not lower the temperature of a non-condensing appliance below the dew point of the flue gas, since the condensate is corrosive.

The heat of combustion calculator gives the energy of a fuel, the boiler size calculator sizes the heat source, the chimney height calculator covers the flue and the dew point calculator helps to avoid condensation in the stack.

Frequently asked questions

What is combustion efficiency?

The combustion efficiency is the part of the fuel energy that is transferred to the water or the air, and not lost with the hot flue gas. It does not include the losses by the casing and the radiation, so it is higher than the overall efficiency of the appliance. It is the figure that a technician reads on the combustion analyzer after a tune-up, and it is the best way to see if a burner is adjusted.

What is the Siegert formula?

The Siegert formula estimates the stack loss as q = (Tf − Ta) × (A2 / (21 − O₂) + B), with the temperatures in degrees Celsius or in kelvin, the oxygen in percent, and the constants A2 and B that depend on the fuel. For natural gas, A2 is 0.66 and B is 0.009. For heating oil, they are 0.68 and 0.007, and for propane 0.63 and 0.008. The efficiency is 100 minus this loss. It is an approximation for dry flue gas.

What is the right level of excess air?

The burner needs more air than the theoretical amount to burn all the fuel. Too little air makes carbon monoxide and soot. Too much air cools the flame and carries heat up the stack. For a gas burner, 10% to 30% excess air, which is 2% to 5% oxygen, is a good range. Oil burners need a bit more, and modern modulating burners work with less.

What are the limits of this calculator?

It gives the dry flue gas loss only. It does not include the loss of the latent heat of the water vapor in non-condensing appliances, the unburned fuel, the radiation of the boiler or the cycling losses. A condensing boiler can have an efficiency above 100% on the lower heating value basis. Use a calibrated analyzer, and have a qualified technician adjust the burner.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.