The confined space purge calculator gives the air changes and the time to dilute a contaminant to a target concentration, with a mixing factor, and the fan size to do it in 30 minutes.
How the calculation works
- Enter the volume of the space and the airflow of the fan.
- Enter the starting and the target concentrations of the contaminant and the quality of the mixing.
- The calculator gives the air changes needed, the purge time and the airflow for a purge in 30 minutes.
Example
A tank of 5,000 ft³ has a contaminant at 2,000 ppm, which must go down to 10 ppm, with a fan of 800 cfm and fair mixing (factor 3). The number of air changes is K ln(C0 / C) = 3 × ln(200) = 15.89. The purge time is 15.89 × 5,000 / 800 = 99.3 min. To purge in 30 minutes, the fan would need 2,649 cfm.
Why it matters
The calculator helps safety officers, contractors, tank and vessel crews and students to plan the ventilation of a confined space before entry, to size a fan or compare fans, and to understand why the mixing and the position of the openings matter.
Good to know
Put the air inlet and the outlet at opposite ends of the space, and blow the clean air toward the far end. Start with the worst-case concentration and a conservative mixing factor. Test the atmosphere with a calibrated meter before the entry and keep the ventilation and the monitoring running during the work, since the purge does not remove a source that keeps releasing the contaminant. Keep a written record of the readings, the fan flow and the time, and make sure that the exhaust is discharged to a safe place away from the air intake of the fan and of nearby buildings.