Confined space purge time and air changes calculator

Enter the space volume, the fan airflow, the starting and target concentrations and the mixing to get the air changes, the purge time and the fan size for a set time.

Updated on
Your inputs
ft³

Value out of range

cfm

Value out of range

ppm

Value out of range

ppm

Value out of range

Results

Purge time

99.3 min

A very long purge: use a larger fan or more points of ventilation
Air changes needed
15.89
Airflow to purge in 30 minutes
2,649 cfm

The confined space purge calculator gives the air changes and the time to dilute a contaminant to a target concentration, with a mixing factor, and the fan size to do it in 30 minutes.

How the calculation works

  • Enter the volume of the space and the airflow of the fan.
  • Enter the starting and the target concentrations of the contaminant and the quality of the mixing.
  • The calculator gives the air changes needed, the purge time and the airflow for a purge in 30 minutes.

Example

A tank of 5,000 ft³ has a contaminant at 2,000 ppm, which must go down to 10 ppm, with a fan of 800 cfm and fair mixing (factor 3). The number of air changes is K ln(C0 / C) = 3 × ln(200) = 15.89. The purge time is 15.89 × 5,000 / 800 = 99.3 min. To purge in 30 minutes, the fan would need 2,649 cfm.

Why it matters

The calculator helps safety officers, contractors, tank and vessel crews and students to plan the ventilation of a confined space before entry, to size a fan or compare fans, and to understand why the mixing and the position of the openings matter.

Good to know

Put the air inlet and the outlet at opposite ends of the space, and blow the clean air toward the far end. Start with the worst-case concentration and a conservative mixing factor. Test the atmosphere with a calibrated meter before the entry and keep the ventilation and the monitoring running during the work, since the purge does not remove a source that keeps releasing the contaminant. Keep a written record of the readings, the fan flow and the time, and make sure that the exhaust is discharged to a safe place away from the air intake of the fan and of nearby buildings.

The air changes calculator gives the ventilation rate of a room, the garage ventilation calculator gives the exhaust for a garage, the indoor CO2 ventilation calculator gives the air needed for people and the kitchen hood calculator gives the exhaust of a hood.

Frequently asked questions

How does the purge work?

When clean air is blown into a closed space, the contaminant is diluted and removed with the air that leaves. With perfect mixing, the concentration falls as an exponential, C = C0 e^(−Q t / V). The time to go from the starting concentration to the target is therefore t = (V / Q) ln(C0 / C), where V / Q is the time for one air change. A number of air changes of 4 to 6 reduces a concentration by a factor of 50 to 400.

What is the mixing factor?

In a real space the air does not mix perfectly. Part of the clean air can go straight to the outlet and leave pockets of contaminated air. The mixing factor multiplies the ideal time, from 1 for ideal mixing to 3 for fair mixing and 5 or more for poor mixing, such as a long narrow tank with the inlet and outlet side by side. Put the inlet and the outlet at opposite ends, and use ducts to reach the far corners.

What concentration should I target?

The target depends on the contaminant: below the exposure limit of the toxic gas, below 10 % of the lower explosive limit for flammable gas, and at 19.5 to 23.5 % oxygen for the atmosphere. The standards for permit-required confined spaces require testing the air before entry and during the work with a calibrated gas detector. The calculator gives only the time of the purge, not the permission to enter.

What does the calculator leave out?

The calculator leaves out the continuing release of the contaminant from sludge, residues, welding or coatings, which keeps the concentration up while the fan runs. It also assumes a gas as dense as air, while a heavy gas stays at the bottom and a light one at the top. Use the continuous ventilation and monitoring that your safety procedure and the standard require, and the advice of the competent person for the space.