Skip to content
Omnikalc

Enclosed garage ventilation exhaust airflow calculator

Enter the floor area, the ceiling height, the exhaust rate and the capacity of a fan to get the exhaust airflow, the air changes per hour and the number of fans.

Updated on
Your inputs
ft²

Value out of range

ft

Value out of range

cfm/ft²

Value out of range

cfm

Value out of range

Results

Required exhaust airflow

9,000 cfm

Air changes per hour
4.5 ACH
Number of exhaust fans
3
Airflow per fan
3,000 cfm

The enclosed garage ventilation calculator gives the exhaust airflow in cfm, the air changes per hour, the number of exhaust fans and the airflow per fan for an enclosed parking garage, from the floor area, the ceiling height, the exhaust rate and the capacity of a fan.

How the calculation works

  • Enter the floor area and the ceiling height of the garage.
  • Enter the exhaust rate required, in cfm per square foot, and the capacity of one fan.
  • The calculator finds the airflow, the air changes per hour, the number of fans and the airflow per fan.

Example

An enclosed garage of 12,000 ft² with a ceiling height of 10 ft needs an exhaust airflow of 12,000 × 0.75 = 9,000 cfm. That is 9,000 × 60 / (12,000 × 10) = 4.5 air changes per hour. With fans of 4,000 cfm the garage needs 9,000 / 4,000 = 2.25, rounded up to 3 fans, each moving 3,000 cfm.

Why it matters

The calculator helps mechanical engineers, contractors, building owners, inspectors and designers to estimate the ventilation of a parking garage in the early stage of a project, to compare the number of fans of different sizes, and to check the order of magnitude of a design.

Good to know

Round the number of fans up and add one more fan for the redundancy if the garage is large, so that the failure of one unit does not stop the ventilation. Use the sensors of carbon monoxide to cut the energy use, and put them at the breathing height, near 4 to 6 ft, with one sensor for each 5,000 ft². Provide make-up air so that the garage does not run under a strong negative pressure.

The air changes calculator gives the ventilation of a room, the residential ventilation rate calculator gives the airflow for a house, the indoor CO2 ventilation calculator gives the ventilation needed for the occupants and the duct size calculator gives the size of a duct for an airflow.

Frequently asked questions

What is the required exhaust rate?

The International Mechanical Code and ASHRAE 62.1 require a continuous mechanical exhaust of 0.75 cfm per square foot of floor area for an enclosed parking garage, except when the garage is ventilated according to the level of carbon monoxide. The calculator takes this value as the default, and you can change it if your code or a local rule asks for another rate.

When can the ventilation be reduced?

The code accepts a ventilation that is controlled by carbon monoxide and nitrogen dioxide sensors, with a lower flow when the garage is empty and the full flow when the sensors reach their set point. The system must keep the gas below a limit that the code gives, often 35 ppm of carbon monoxide on average over 8 hours and a maximum of 200 ppm. The calculator gives the full flow for the maximum case.

How should the air flow in the garage?

Place the exhaust points and the supply openings so that the air moves through all the garage, away from the stairs and elevators. Exhaust from the low and the high levels, as carbon monoxide mixes with the air and the vapors of gasoline fall to the floor. Dead zones behind pillars and in corners need a special attention, with jet fans or ducts if the garage is large.

What does the calculator leave out?

The calculator gives the total exhaust flow and the number of fans of a given size. It does not size the ducts, the make-up air, the pressure loss, the fan power or the sensors, and it does not compute the smoke control or the exhaust of the fire. An open parking structure with natural ventilation follows other rules. Ask a mechanical engineer for the design of the system.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.