Duct heat gain and air temperature rise calculator

Enter the airflow, the duct size and length, the insulation, the supply and attic temperatures to get the air temperature rise, the heat gain and the cooling lost.

Updated on
Your inputs
cfm

Value out of range

in

Value out of range

ft

Value out of range

h·ft²·°F/Btu

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

Results

Cooling capacity lost

13.7 %

Large loss: add insulation or move the duct into the conditioned space
Heat transfer area of the duct
293.2 ft²
Number of transfer units
0.057
Air temperature at the end of the run
57.7 °F
Temperature rise of the air
2.75 °F
Heat gain of the duct
2,376 Btu/h

The duct heat gain calculator gives the air temperature at the end of the run, the temperature rise, the heat gain in Btu per hour and the share of the cooling capacity lost of an insulated round duct that passes through an unconditioned space.

How the calculation works

  • Enter the airflow, the diameter and the length of the duct in the unconditioned space and the R-value of its insulation.
  • Enter the supply air temperature, the temperature around the duct and the room temperature.
  • The calculator gives the air temperature at the end of the run, the temperature rise, the heat gain and the cooling capacity lost.

Example

A round duct of 14 in and 80 ft crosses an attic at 105 °F with 800 cfm of air supplied at 55 °F and insulation of R-6. The surface is π × 14 × 80 / 12 = 293.2 ft² and the number of transfer units is 293.2 / 6 / (1.08 × 800) = 0.057. The air leaves at 105 − 50 × e^(−0.057) = 57.7 °F, a rise of 2.75 °F, so the heat gain is 1.08 × 800 × 2.75 = 2,376 Btu/h. For a room at 75 °F, the cooling capacity lost is 2.75 / 20 = 13.7 %.

Why it matters

The calculator helps HVAC designers, energy auditors, contractors and homeowners to see how much cooling a duct in a hot attic loses, to choose the insulation level and to compare a duct in the attic with one inside the conditioned space.

Good to know

Keep the ducts inside the thermal envelope when you can, since a duct in the conditioned space loses almost nothing. Where it has to cross an attic, shorten the run, increase the airflow rate per duct to lower the NTU, and raise the R-value. Seal the joints before insulating them, and avoid compressed or kinked flexible ducts that raise the loss and the pressure drop.

The duct size calculator sizes the duct for the airflow, the duct leakage calculator gives the allowable leakage, the air grille and diffuser calculator sizes the outlets and the sensible heat ratio calculator splits the load between sensible and latent heat.

Frequently asked questions

How is the temperature rise found?

The air in a duct that runs through a warmer space follows an exponential approach to the temperature of that space. The exit temperature is T = Ta − (Ta − Ti) e^(−NTU), where NTU is the heat transfer area divided by the R-value and by the heat capacity rate of the air, 1.08 times the airflow in cfm. This uses the mean wall temperature and is better than the simple method that takes a fixed loss per foot.

Why is the loss a large share of the capacity?

The supply air is only 15 to 20 °F colder than the room, so a rise of a few degrees on the way is a large share of that difference. A rise of 2.75 °F out of 20 °F is 13.7 % of the cooling. Hot attics at 120 °F or more, small ducts with a low airflow, flexible ducts with low R-values and long runs all add to it. The loss is a sensible one, and it adds to the energy of the unit.

What R-value should I use?

Use the R-value of the installed insulation, not the nominal one, because compressed flexible duct loses much of it, and add little for the films. Many codes ask for R-6 to R-8 for ducts in unconditioned spaces, and a hot climate or a long run can justify R-8 or more. The R-value of the duct is the insulation value, and it includes the average of the sags and the bunches.

What does the calculator leave out?

The calculator does not include the duct leakage, which can be larger than the conduction loss and is checked with the duct leakage calculator. It also leaves out the radiation of a hot attic, the sag of the insulation, the heat gain of the duct fittings and the plenum, and the condensation on a cold duct. It takes a round duct, so for a rectangular duct use the perimeter and the length to find the area.