The duct heat gain calculator gives the air temperature at the end of the run, the temperature rise, the heat gain in Btu per hour and the share of the cooling capacity lost of an insulated round duct that passes through an unconditioned space.
How the calculation works
- Enter the airflow, the diameter and the length of the duct in the unconditioned space and the R-value of its insulation.
- Enter the supply air temperature, the temperature around the duct and the room temperature.
- The calculator gives the air temperature at the end of the run, the temperature rise, the heat gain and the cooling capacity lost.
Example
A round duct of 14 in and 80 ft crosses an attic at 105 °F with 800 cfm of air supplied at 55 °F and insulation of R-6. The surface is π × 14 × 80 / 12 = 293.2 ft² and the number of transfer units is 293.2 / 6 / (1.08 × 800) = 0.057. The air leaves at 105 − 50 × e^(−0.057) = 57.7 °F, a rise of 2.75 °F, so the heat gain is 1.08 × 800 × 2.75 = 2,376 Btu/h. For a room at 75 °F, the cooling capacity lost is 2.75 / 20 = 13.7 %.
Why it matters
The calculator helps HVAC designers, energy auditors, contractors and homeowners to see how much cooling a duct in a hot attic loses, to choose the insulation level and to compare a duct in the attic with one inside the conditioned space.
Good to know
Keep the ducts inside the thermal envelope when you can, since a duct in the conditioned space loses almost nothing. Where it has to cross an attic, shorten the run, increase the airflow rate per duct to lower the NTU, and raise the R-value. Seal the joints before insulating them, and avoid compressed or kinked flexible ducts that raise the loss and the pressure drop.