Sensible heat ratio calculator: SHR, supply airflow and moisture to remove

Enter the sensible and latent cooling loads and the supply air temperature difference to get the sensible heat ratio, the total load in Btu/h and tons, the supply airflow in CFM and the moisture to remove.

Updated on
Your inputs
Btu/h

Value out of range

Btu/h

Value out of range

°F

Value out of range

Results

Sensible heat ratio (SHR)

0.800

Sensible load dominates: a standard system fits

Supply airflow

1,111 CFM

Total cooling load
30,000 Btu/h
Total cooling load in tons
2.50 tons
Moisture to remove
5.71 lb/h

The sensible heat ratio tells how much of a cooling load is temperature and how much is humidity. The sensible heat ratio calculator gives the SHR, the total load in Btu/h and tons, the supply airflow in CFM and the moisture that the system must remove.

How the calculation works

  • Enter the sensible cooling load (the heat that changes the air temperature) and the latent cooling load (the heat of the moisture to condense) of the space, from a load calculation.
  • Enter the temperature difference between the room and the supply air, typically 18 °F to 22 °F for comfort cooling.
  • The calculator computes the sensible heat ratio SHR = Qs / (Qs + Ql), the total load and the equivalent tons of cooling.
  • It then gives the supply airflow CFM = Qs / (1.08 × ΔT) and the moisture removal in lb/h, using about 1,050 Btu per pound of water condensed.

Example

A room has a sensible load of 24,000 Btu/h and a latent load of 6,000 Btu/h, with a temperature difference of 20 °F. The sensible heat ratio is 24,000 / 30,000 = 0.80. The total load is 30,000 Btu/h, or 2.50 tons. The supply airflow is 24,000 / (1.08 × 20) = 1,111 CFM. The moisture to remove is 6,000 / 1,050 = 5.71 lb/h, or about 0.7 gallons per hour.

Why it matters

The calculator helps HVAC designers, technicians and students to choose air conditioning equipment that fits the real mix of sensible and latent loads, to size the airflow and to see when a room needs extra dehumidification. It gives the numbers that the psychrometric chart gives, in a few seconds.

Good to know

Compare the SHR of the room with the SHR of the equipment at the design conditions. If the room SHR is lower, consider a lower airflow per ton, a variable speed system or a separate dehumidifier. Do not use a much larger unit than necessary, since an oversized unit short cycles and removes less humidity.

The humidity ratio calculator gives the moisture content of air, the latent heat calculator covers the phase changes, the cooling degree days calculator estimates the annual cooling demand and the HVAC superheat and subcooling calculator checks the refrigerant charge.

Frequently asked questions

What is the sensible heat ratio?

The sensible heat ratio (SHR) is the part of the total cooling load that is sensible heat: SHR = Qs / (Qs + Ql). Sensible heat changes the temperature of the air that you can measure with a thermometer. Latent heat comes from the moisture in the air, and it must be removed by condensation on the coil. An SHR of 0.80 means that 80% of the load lowers the temperature and 20% removes the humidity.

What is a typical SHR?

For comfort cooling in a dry climate, the SHR is 0.85 to 0.95. In an average climate it is 0.75 to 0.85, and in a humid climate or in a room with many people it can be 0.65 to 0.75 or less. A standard residential air conditioner has a rated SHR of about 0.70 to 0.80 at the usual conditions. If the room SHR is lower than the SHR of the equipment, the room will be too humid.

Where do the 1.08 and the 1,050 come from?

The constant 1.08 is 60 min/h × 0.075 lb/ft³ × 0.24 Btu/lb·°F for the sensible heat of standard air in Btu/h per CFM and per °F. The value 1,050 Btu/lb is the latent heat of condensation of the water vapor, which is about 1,050 to 1,060 Btu per pound at room conditions. They are standard approximations that are valid near sea level and normal temperatures.

What are the limits of this calculator?

It uses constants for standard air, and it gives a first estimate of the airflow and the moisture. A precise design uses the psychrometric chart, the coil data and the real condition of the air, and it takes the altitude into account. The airflow can also be limited by the duct size, the noise, or the minimum ventilation rate that the code requires.