Boiler economizer calculator: fuel and cost saved by recovering stack heat

Enter the flue gas flow and temperatures, the feedwater flow, the boiler efficiency, the fuel cost and the operating hours to get the heat recovered, the feedwater temperature rise, the fuel saved and the annual savings.

Updated on
Your inputs
lb/h

Value out of range

Btu/lb·°F

Value out of range

°F

Value out of range

°F

Value out of range

lb/h

Value out of range

°F

Value out of range

%

Value out of range

$/MMBtu

Value out of range

h

Value out of range

Results

Heat recovered

1,950,000 Btu/h

Feedwater temperature leaving
263.3 °F
Fuel saved
2.378 MMBtu/h
Annual savings
114,146 $/year
Flue gas margin over the natural gas water dew point (135 °F)
165 °F
Gas stays above the dew point of the flue gas

The boiler economizer calculator gives the heat recovered from the flue gas, the feedwater temperature leaving the economizer, the fuel saved, the annual savings and the margin over the dew point, for a given boiler and stack.

How the calculation works

  • Enter the flue gas flow rate and its specific heat, with the temperatures of the gas entering and leaving the economizer.
  • Enter the feedwater flow rate and its entering temperature, and the boiler efficiency used to convert the heat to fuel.
  • Enter the fuel cost and the operating hours per year.
  • The calculator gives the heat recovered Q = m cp (Tin − Tout), the feedwater temperature after the economizer, the fuel saved, the annual savings and the margin of the gas outlet over the dew point.

Example

A boiler stack carries 50,000 lb/h of gas at 450 °F, and an economizer cools it to 300 °F. The heat recovered is 50,000 × 0.26 × 150 = 1,950,000 Btu/h. It heats 45,000 lb/h of feedwater from 220 °F to 263.3 °F. At a boiler efficiency of 82%, the fuel saved is 2.378 MMBtu/h. For 6,000 h at $8/MMBtu, the savings are $114,146 per year, and the gas leaves 165 °F above the dew point.

Why it matters

The calculator helps energy managers, boiler operators, plant engineers and consultants to estimate quickly the benefit of an economizer, to compare it with other efficiency measures and to prepare a business case. It also helps check an offer from a supplier against the physical limits.

Good to know

Use the real flue gas flow from a combustion analysis or the stack data. Keep the gas outlet above the dew point unless the economizer is a condensing unit. Check that the feedwater flow is enough to absorb the heat. Add the cost of the stack fan and of the cleaning when you compute the payback.

The combustion efficiency calculator gives the stack loss, the heat exchanger LMTD calculator sizes the exchanger, the specific heat calculator covers the heat of a fluid and the boiler blowdown calculator covers another heat recovery point.

Frequently asked questions

What does an economizer do?

A boiler economizer is a heat exchanger in the flue gas duct that preheats the boiler feedwater with heat that would be lost through the stack. Each 40 °F (22 °C) drop in the stack temperature raises the boiler efficiency by about 1%. Typical stack temperatures fall from 450 °F to 300 °F or lower, which brings a fuel saving of 4 to 6% for a steam boiler.

How low can the gas be cooled?

The flue gas must stay above its dew point, otherwise the water in it, and the acids from sulfur in the fuel, condense and corrode the tubes. For natural gas the water dew point is about 135 °F (57 °C), and for oil and coal the acid dew point is 250 to 300 °F. Condensing economizers made of stainless steel or other corrosion-resistant materials work below the dew point and recover the latent heat.

How is the fuel saving computed?

The heat recovered goes into the feedwater, so the boiler needs less heat from the fuel. The fuel saved is the heat recovered divided by the boiler efficiency. Multiplying by the operating hours and the fuel price gives the annual saving. The investment payback of an economizer is typically between 1 and 3 years for a boiler that runs more than 4,000 hours per year.

What are the practical limits?

The feedwater must absorb the heat: its flow and temperature set how much can be recovered, and the water temperature must stay safely under the boiling point at the pressure of the economizer to avoid steaming. The economizer also adds a draft loss on the gas side, which may require a stack fan. Soot on the tubes reduces the heat transfer, so the gas side must be cleaned regularly.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.