The fire water storage tank calculator gives the sprinkler flow, the total demand with the hose stream, the water for the duration, the tank volume with a reserve and the water depth in a round tank.
How the calculation works
- Enter the sprinkler density and the design area, the hose stream allowance and the duration of the supply.
- Enter the reserve for unusable water and the diameter of a round tank.
- The calculator gives the sprinkler flow, the total demand, the volume of water and the water depth in the tank.
Example
A sprinkler system of 0.20 gpm/ft² over 1,500 ft² flows 300 gpm. With a hose stream allowance of 250 gpm the total demand is 550 gpm. For 90 minutes the water needed is 550 × 90 = 49,500 gal, and with 10 % of unusable water and reserve the tank must hold 54,450 gal. In a round tank of 30 ft the water is 10.30 ft deep.
Why it matters
The calculator helps fire protection engineers, designers, building owners and plant managers to size the storage of a fire sprinkler system that is not fed by a city main, and to size a round tank.
Good to know
Take the density, the area, the hose stream and the duration from the standard and the hazard class of your project, and check them with the authority having jurisdiction. Compare the tank volume with the capacity of the fire pump and the size of the suction pipe. Plan for freeze protection, a level indicator and a refill line, and have the tank inspected every year. Keep the calculation with the hydraulic design of the sprinkler system, since the authority will want to see how the duration and the allowance were chosen, and update it when the hazard of the building changes.