Fire water storage tank volume calculator

Enter the sprinkler density and area, the hose stream, the duration and the reserve to get the demand, the tank volume and the water depth.

Updated on
Your inputs
gpm/ft²

Value out of range

ft²

Value out of range

gpm

Value out of range

min

Value out of range

%

Value out of range

ft

Value out of range

Results

Tank volume with the reserve

54,450 gal

Sprinkler flow
300 gpm
Total demand
550 gpm
Water for the duration
49,500 gal
Water depth in the round tank
10.30 ft

The fire water storage tank calculator gives the sprinkler flow, the total demand with the hose stream, the water for the duration, the tank volume with a reserve and the water depth in a round tank.

How the calculation works

  • Enter the sprinkler density and the design area, the hose stream allowance and the duration of the supply.
  • Enter the reserve for unusable water and the diameter of a round tank.
  • The calculator gives the sprinkler flow, the total demand, the volume of water and the water depth in the tank.

Example

A sprinkler system of 0.20 gpm/ft² over 1,500 ft² flows 300 gpm. With a hose stream allowance of 250 gpm the total demand is 550 gpm. For 90 minutes the water needed is 550 × 90 = 49,500 gal, and with 10 % of unusable water and reserve the tank must hold 54,450 gal. In a round tank of 30 ft the water is 10.30 ft deep.

Why it matters

The calculator helps fire protection engineers, designers, building owners and plant managers to size the storage of a fire sprinkler system that is not fed by a city main, and to size a round tank.

Good to know

Take the density, the area, the hose stream and the duration from the standard and the hazard class of your project, and check them with the authority having jurisdiction. Compare the tank volume with the capacity of the fire pump and the size of the suction pipe. Plan for freeze protection, a level indicator and a refill line, and have the tank inspected every year. Keep the calculation with the hydraulic design of the sprinkler system, since the authority will want to see how the duration and the allowance were chosen, and update it when the hazard of the building changes.

The needed fire flow calculator gives the flow for the fire department, the sprinkler system demand calculator gives the pressure and the flow of the sprinklers, the fire pump rating curve calculator checks the pump and the elevated water tank calculator sizes the storage of a water supply.

Frequently asked questions

How is the volume of the fire water tank found?

The volume is the total demand times the duration. The demand is the sprinkler flow, which is the density times the design area, plus the hose stream allowance for the fire department, and the duration is the time the supply must last. NFPA 13 gives hose stream allowances and durations by hazard: for example 100 gpm for 30 minutes for light hazard, and 250 gpm for 60 to 90 minutes for ordinary hazard. Extra hazard asks for 500 gpm and 90 to 120 minutes.

Why add a reserve?

A tank cannot be emptied to the last gallon. The suction pipe sits above the floor, a vortex breaker takes some depth and sediment collects at the bottom. A reserve of 5 to 15 % is added for this, and for the loss by evaporation, the leaks and the tolerance of the volume. Some authorities also ask for a margin for the replenishment, or credit the refill rate of the city supply during the fire.

What is the effect of the water supply?

If a reliable water main can refill the tank during the fire, the authority having jurisdiction may allow a smaller tank, since the refill rate is subtracted from the demand. The calculator takes the whole demand from the tank, which is the safe case of a tank with no refill. For a tank with a refill, subtract the available inflow from the demand before the volume.

What does the calculator leave out?

The calculator does not size the fire pump, the suction piping, the minimum water level above the pump, the freeze protection or the seismic and wind design of the tank. It also does not add the water for a standpipe, a foam system or a second hazard in the same building. Those are calculated with the standards of your authority, such as NFPA 13, NFPA 22 and NFPA 20.

Was this calculator helpful?

Thanks for your feedback!