Elevated water tank calculator: storage volume for a community water system

Enter the population, the water use, the maximum day factor, the fire flow and duration, the emergency fraction and the water depth to get the equalization, fire and emergency storage, the total volume and the tank diameter.

Updated on
Your inputs

Value out of range

gal/day

Value out of range

Value out of range

gpm

Value out of range

h

Value out of range

Value out of range

ft

Value out of range

Results

Total storage required

840,000 gal

Maximum day demand
1,200,000 gal
Equalization storage (25 % of the maximum day)
300,000 gal
Fire storage
240,000 gal
Emergency storage
300,000 gal
Diameter of a cylindrical tank
69.0 ft

The elevated water tank calculator gives the maximum day demand, the equalization, fire and emergency storage, the total volume and the diameter of a water distribution tank, from the population, the use, the fire flow and the water depth.

How the calculation works

  • Enter the population served, the average daily use per person and the maximum day factor.
  • Enter the fire flow and its duration, the emergency storage as a fraction of the maximum day demand and the usable water depth of the tank.
  • The calculator finds the maximum day demand, the equalization, fire and emergency storage, the total storage and the diameter of a cylindrical tank.

Example

A town of 5,000 people uses 120 gal/day each, with a maximum day factor of 2. The maximum day demand is 5,000 × 120 × 2 = 1,200,000 gal. The equalization storage is 25 % of it, 300,000 gal. The fire flow of 2,000 gpm for 2 h gives 2,000 × 120 = 240,000 gal, and the emergency storage of 25 % gives 300,000 gal. The total is 840,000 gal. With a usable depth of 30 ft, the diameter is √(4 × 840,000 / 7.48 / 30 / π) = 69.0 ft.

Why it matters

The calculator helps water utility engineers, municipal planners, developers and students to estimate the storage needed for a new community or an extension, to compare the contribution of each type of storage and to size a first tank.

Good to know

Use the real demand data of the system and the maximum day factor of the region. Check the fire flow with the fire marshal, and the water age in the tank so that the chlorine residual is kept. Use the local rules for the emergency storage and consider more than one tank.

The needed fire flow calculator gives the fire flow, the hydrant flow test calculator gives the available flow, the detention time calculator checks the retention time and the pump power calculator sizes the pumps.

Frequently asked questions

Why does a water system need a storage tank?

An elevated or ground tank keeps the pressure in the network, supplies the peak demand when it is higher than the capacity of the sources and the pumps, gives a reserve for the fires and keeps water in case of a power failure or a break. It also lets the pumps run at a steady rate. The tank volume is the sum of the equalization (or operational), fire and emergency storage.

How is each storage calculated?

The equalization storage supplies the difference between the peak hour demand and the supply rate, and is often taken as 25 % of the maximum day demand when no data exist. The fire storage is the fire flow times its duration, as given by the fire code or the insurance rules, from 2 to 10 hours depending on the flow. The emergency storage is a reserve for the failures, often 25 to 100 % of the average day demand or a fraction of the maximum day, according to the state rules.

How is the tank dimensioned?

For a cylindrical tank, the diameter comes from the volume and the usable depth of water, which is the height between the low level (the minimum pressure) and the overflow. The location and the height of the tank set the pressure in the network, which should be between about 35 and 100 psi (240 and 690 kPa) at the services. The volume is often provided in a few tanks, so that one can be out of service.

What are the limits of the calculator?

The calculator is for a first estimate of the volume. It does not include the pressure zones, the detailed demand pattern of the day, the water age and the quality in the tank, the seismic and the wind design, the costs or the local regulations. The storage requirements of the health authority and of the fire code must be followed, and the design must be made by a qualified engineer.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.