Fire pump rating calculator: NFPA 20 curve points and system demand

Enter the rated flow and pressure, the system demand and the efficiency to get the 150 % flow point, the minimum pressure, the shutoff pressure, the power and the demand ratios.

Updated on
Your inputs
gpm

Value out of range

psi

Value out of range

gpm

Value out of range

psi

Value out of range

Value out of range

Results

Ratio of the demand flow to the rated flow

0.85

Within the rating of the pump
Flow at 150 % of the rating
1,500 gpm
Minimum pressure at 150 % flow
65.0 psi
Maximum shutoff pressure
140.0 psi
Power at 150 % flow
81.3 hp
Ratio of the demand pressure to the rated pressure
0.90
Within the rating of the pump

The fire pump rating calculator gives the 150 % flow point, the minimum pressure at this flow, the maximum shutoff pressure, the power at 150 % flow and the ratios of the demand to the rating of a fire pump, from its rated flow and pressure and the system demand.

How the calculation works

  • Enter the rated flow and the rated net pressure of the fire pump.
  • Enter the flow and the pressure demanded by the system at the pump, and the efficiency of the pump.
  • The calculator finds the 150 % flow point, the minimum pressure there, the maximum shutoff pressure, the power and the ratios of the demand.

Example

A fire pump is rated at 1,000 gpm and 100 psi. At 150 % of the flow, that is 1,500 gpm, it must still give at least 65 % of the pressure, 65.0 psi, and at zero flow the pressure must not exceed 140 %, 140.0 psi. With an efficiency of 0.70, the power at 150 % is 1,500 × 65 / (1,714 × 0.70) = 81.3 hp. A system that needs 850 gpm at 90 psi is at 0.85 of the rated flow and 0.90 of the rated pressure.

Why it matters

The calculator helps fire protection engineers, sprinkler contractors, building owners and students to check the points that a fire pump must meet, to compare the demand of a sprinkler or standpipe system with the rating of a pump, and to estimate the driver power needed at 150 % of the flow.

Good to know

Compare the real test curve of the pump with the acceptance values of the standard when the pump is installed, and test it every year at the flow of 100 % and 150 %. Keep the water supply and the suction piping sized for the 150 % flow, and keep the pump room heated and ventilated. Record the readings so that a drop in performance is seen early.

The hydrostatic test pressure calculator gives the test pressure of a piping, the water main flushing time and volume calculator plans the flushing of the water pipes, the NPSH calculator checks the suction of a pump and the pipe support spacing calculator checks the supports of the pipes.

Frequently asked questions

What are the points of the curve of a fire pump?

The standard NFPA 20 defines a few points on the performance curve of a fire pump. At the rated flow, the pump gives the rated net pressure. At 150 % of the rated flow, it must give at least 65 % of the rated pressure. At shutoff, with no flow, the pressure must not be more than 140 % of the rated pressure. The pump must follow a smooth curve between these points.

How is a pump chosen for a system?

The pump is chosen from the standard sizes so that its rated flow is at least equal to the demand of the system, and so that the system demand point is under the curve of the pump. The demand is made of the sprinkler or the standpipe flow, the hose allowance and the pressure needed at the most remote point, plus the losses in the pipes and the elevation. The calculator compares the demand to the rated values.

Why is the power at 150 % flow computed?

The driver of the pump, an electric motor or a diesel engine, must be able to run the pump at 150 % of its rated flow without overload. The power is the flow times the pressure divided by a constant of 1,714 in imperial units and by the efficiency. In metric units, the flow in cubic meters per second times the pressure in kilopascals, divided by the efficiency, gives kilowatts.

What are the limits of the calculator?

The calculator uses the three standard points and a simplified demand check. It does not draw the full curve of a pump, check the suction conditions and the available NPSH, the pressure of the water supply, the jockey pump, the controller, the relief valve or the testing arrangement. The selection of a fire pump must follow the standard and the approval of the authority having jurisdiction.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.