The fire pump rating calculator gives the 150 % flow point, the minimum pressure at this flow, the maximum shutoff pressure, the power at 150 % flow and the ratios of the demand to the rating of a fire pump, from its rated flow and pressure and the system demand.
How the calculation works
- Enter the rated flow and the rated net pressure of the fire pump.
- Enter the flow and the pressure demanded by the system at the pump, and the efficiency of the pump.
- The calculator finds the 150 % flow point, the minimum pressure there, the maximum shutoff pressure, the power and the ratios of the demand.
Example
A fire pump is rated at 1,000 gpm and 100 psi. At 150 % of the flow, that is 1,500 gpm, it must still give at least 65 % of the pressure, 65.0 psi, and at zero flow the pressure must not exceed 140 %, 140.0 psi. With an efficiency of 0.70, the power at 150 % is 1,500 × 65 / (1,714 × 0.70) = 81.3 hp. A system that needs 850 gpm at 90 psi is at 0.85 of the rated flow and 0.90 of the rated pressure.
Why it matters
The calculator helps fire protection engineers, sprinkler contractors, building owners and students to check the points that a fire pump must meet, to compare the demand of a sprinkler or standpipe system with the rating of a pump, and to estimate the driver power needed at 150 % of the flow.
Good to know
Compare the real test curve of the pump with the acceptance values of the standard when the pump is installed, and test it every year at the flow of 100 % and 150 %. Keep the water supply and the suction piping sized for the 150 % flow, and keep the pump room heated and ventilated. Record the readings so that a drop in performance is seen early.
Related tools
The hydrostatic test pressure calculator gives the test pressure of a piping, the water main flushing time and volume calculator plans the flushing of the water pipes, the NPSH calculator checks the suction of a pump and the pipe support spacing calculator checks the supports of the pipes.