Skip to content
Omnikalc

Glycol freeze protection mix and flow correction calculator

Enter the volume of the system, the lowest outdoor temperature and the safety margin to get the percentage of propylene glycol, the volumes of glycol and water, and the extra flow.

Updated on
Your inputs
gal

Value out of range

°F

Value out of range

°F

Value out of range

Results

Propylene glycol by volume

31.4 %

Volume of glycol to add
125.7 gal
Volume of water
274.3 gal
Heat capacity compared with water
0.91
Extra flow to carry the same heat
6.6 %

The glycol freeze protection calculator gives the percentage of propylene glycol, the volume of glycol to add, the volume of water, the heat capacity compared with water and the extra flow needed, from the volume of the hydronic system, the lowest outdoor temperature and a safety margin.

How the calculation works

  • Enter the volume of the hydronic system and the lowest outdoor temperature.
  • Enter the safety margin you want below that temperature.
  • The calculator finds the percentage of glycol, the volume of glycol and of water, the heat capacity and the extra flow.

Example

A system of 400 gal must be protected down to 10 °F with a margin of 5 °F, so the mixture must resist 32 − (10 − 5) = 27 °F of drop. The calculator gives 31.4 % of propylene glycol, that is 125.7 gal of glycol and 274.3 gal of water. The heat capacity is 0.91 times that of water, so the flow must rise by 6.6 % to carry the same heat.

Why it matters

The calculator helps heating contractors, plumbers, facility managers, solar installers and homeowners to prepare a snow melt loop, a rooftop coil, a solar loop or a seasonal boiler for the winter, to buy the right amount of glycol, and to see how much the mix reduces the heat transfer of the system.

Good to know

Drain and flush the system, then mix the glycol with clean or distilled water in a separate tank before you fill the circuit, because a layer of pure glycol may stay at the bottom. Test the freeze point with a refractometer after the fill, and check it every year. Do not use more glycol than needed, because every extra percent reduces the heat transfer and raises the pumping cost.

The freezing point calculator gives the freezing point of a solution, the heat tracing power calculator sizes a trace heater for a pipe, the hydronic expansion tank calculator sizes the tank of a loop and the pipe volume calculator gives the volume of a pipe run.

Frequently asked questions

How much glycol do I need?

The freeze protection depends on the percentage of glycol in the water. About 30 % of propylene glycol by volume protects against freezing to about 10 °F, and about 50 % goes below −25 °F. The calculator uses a curve fitted on typical tables and adds the safety margin that you choose to the lowest outdoor temperature.

Why does the flow have to increase?

A glycol mixture carries less heat per gallon than water, and it is also thicker. At the same flow, the same system moves less heat. The calculator estimates the heat capacity and the density of the mixture, and gives the extra flow that carries the same heat, which also means a higher pump head because the fluid is more viscous.

Burst protection or freeze protection?

Freeze protection stops the first ice crystals, and it needs a higher percentage. Burst protection only prevents the pipes from breaking, because a slush forms but does not expand as hard, and it needs less glycol. For a system that must keep flowing, as in a solar loop or a snow melt system, choose the freeze protection.

What are the limits of the calculator?

The calculator is for propylene glycol in water and uses a simple fit with a maximum of 60 %. It does not replace the table of the supplier, which depends on the inhibitors, the dilution water and the temperature. Test the mix with a refractometer, replace the fluid when the inhibitor is spent, and never use automotive antifreeze in a potable water system.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.