Heat tracing power calculator: heating cable output for an insulated pipe

Enter the pipe size, insulation, maintenance and ambient temperatures, the safety factor and the length to get the heat loss, the heating cable output in watts per foot, the total power and the current.

Updated on
Your inputs
in

Value out of range

in

Value out of range

Btu·in/h·ft²·°F

Value out of range

°F

Value out of range

°F

Value out of range

ft

Value out of range

V

Value out of range

Results

Heating cable output required (with safety factor)

7.33 W/ft

Cable output within the range of standard heating cables
Heat loss of the insulated pipe
19.23 Btu/h·ft
Total heater power
1.47 kW
Current at the supply voltage
6.11 A

The heat tracing power calculator gives the heat loss of an insulated pipe, the heating cable output in watts per foot with a safety factor, the total power and the current, to keep a pipe above a minimum temperature when it is cold.

How the calculation works

  • Enter the outside diameter of the pipe, the thickness and the thermal conductivity of the insulation (0.25 Btu·in/h·ft²·°F for mineral wool or foam).
  • Enter the temperature to maintain and the lowest ambient temperature of the site, and choose a safety factor.
  • Enter the length of traced pipe and the supply voltage.
  • The calculator finds the heat loss per foot q = 2π k (Tm − Ta) / ln(Do / Dp), converts it to watts, applies the safety factor and gives the cable output to install, the total power and the current.

Example

A 2.375 in pipe has 1.5 in of insulation with k = 0.25 and must be kept at 100 °F when the air is −20 °F. The loss is 2π × (0.25 / 12) × 120 / ln(5.375 / 2.375) = 19.23 Btu/h·ft, or 5.64 W/ft. With a safety factor of 1.3, the cable output is 7.33 W/ft. For 200 ft of pipe, the total power is 1.47 kW, and the current at 240 V is 6.11 A.

Why it matters

The calculator helps electricians, plant and building engineers, and facility managers to size a freeze protection or process temperature maintenance system, to compare insulation thicknesses and to estimate the electrical load and the running cost. It is a first check before using the cable manufacturer’s selection tables.

Good to know

Use the lowest ambient temperature of the site with the real wind. Choose a conservative thermal conductivity for the insulation as it ages and gets wet. Add cable for valves and supports. Use ground fault protection, as the heating cable circuits require it, and check the cable’s maximum temperature for plastic pipe or hazardous areas.

The heat loss calculator covers general heat loss, the Joule heating calculator links the electric power to heat, the wire ampacity calculator sizes the supply cable and the specific heat calculator covers heating a fluid.

Frequently asked questions

How is the power of a heat tracing cable chosen?

The cable must replace the heat that the pipe loses to the air at the coldest design temperature. The heat loss per foot depends on the temperature difference, the insulation thickness and its conductivity. The cable output is then increased by a safety factor of 10 to 50%, since insulation gets wet and ages, and the wind increases the loss. The next standard cable rating above the result is chosen.

Why is the insulation so important?

The loss is inversely proportional to the logarithm of the diameter ratio, so doubling the insulation thickness does not halve the loss, but it reduces it a lot. Good insulation reduces the cable rating, the number of circuits and the operating cost. For a pipe that needs 20 W/ft with 1 in of insulation, 2 in of insulation can lower this to about 12 W/ft.

Does the calculator include pipe fittings?

No. Valves, flanges, pipe supports and instruments lose more heat than a straight pipe, because their surface area is larger or they are not insulated as well. Add extra cable length at each valve and support (often a loop of 1 to 3 feet, or about 1 m), and use a higher safety factor for pipes with many fittings or when the insulation might be damaged.

What is the maximum circuit length?

The maximum length of a circuit depends on the cable type, the circuit breaker and the supply voltage, and it is given in the cable manufacturer’s tables. Self-regulating cables raise their output as the pipe gets colder, which makes the start-up current high. The current shown here is the steady current at the design output and not the starting current, so use the maker’s data to size the breaker.