Skip to content
Omnikalc

Insulated pipe heat loss and annual cost calculator

Enter the pipe, the insulation, the temperatures, the length and the fuel to get the heat loss per foot, the surface temperature and the yearly cost.

Updated on
Your inputs
in

Value out of range

in

Value out of range

Btu·in/h·ft²·°F

Value out of range

°F

Value out of range

°F

Value out of range

Btu/h·ft²·°F

Value out of range

ft

Value out of range

h

Value out of range

$/MMBtu

Value out of range

%

Value out of range

Results

Fuel cost of the loss per year

492 $

Heat loss per foot of pipe
16.4 Btu/h·ft
Total heat loss
3,277 Btu/h
Outer surface temperature
77.8 °F
Energy lost per year
26.2 MMBtu

The insulated pipe heat loss calculator gives the heat loss per foot, the total heat loss, the outer surface temperature, the energy lost per year and the fuel cost of the loss of a hot pipe, from its size, the insulation, the temperatures and the length.

How the calculation works

  • Enter the outside diameter of the pipe, the thickness and the conductivity of the insulation.
  • Enter the fluid and ambient temperatures, the film coefficient, the length and the operating hours.
  • Enter the fuel price and the plant efficiency. The calculator gives the heat loss, the surface temperature and the yearly cost.

Example

A 2 in pipe (outside diameter 2.375 in) with 1.5 in of insulation of conductivity 0.25 Btu·in/h·ft²·°F carries water at 180 °F in air at 70 °F with a film coefficient of 1.5. The thermal resistance per foot is 6.239 + 0.474 = 6.713 h·ft·°F/Btu, so the loss is 110 / 6.713 = 16.4 Btu/h per foot, and 3,277 Btu/h for 200 ft. The surface is at 77.8 °F. Over 8,000 h this is 26.2 MMBtu, and at $15/MMBtu and 80 % efficiency it costs $492 a year.

Why it matters

The calculator helps mechanical engineers, energy auditors, plant managers and contractors to price the heat lost by a steam or hot water line, to compare insulation thicknesses and to check the surface temperature for the safety of the personnel.

Good to know

Keep the surface temperature under about 140 °F for personnel protection in accessible places, and add a jacket to protect the insulation from water and impact. Insulate the valves, the flanges and the supports with removable covers, since the bare fittings can lose as much as several feet of pipe. Compare the payback of an extra layer with the price of the fuel and the hours of use before you decide.

The pipe insulation condensation calculator checks the cold pipes, the critical insulation radius calculator gives the radius where the insulation starts to help, the pipe expansion loop calculator sizes the expansion of a hot line and the hot water recirculation calculator gives the loss of a loop.

Frequently asked questions

How is the heat loss of a pipe found?

The heat flows through the insulation by conduction and from the outer surface to the air by convection and radiation. For a cylinder the resistances in series per unit length are ln(r2 / r1) / (2 π k) for the insulation and 1 / (2 π r2 h) for the surface film. The loss per unit length is the temperature difference divided by their sum. The calculator neglects the resistances of the pipe wall and of the inside film, which are very small.

What conductivity should I use?

Typical values at a mean temperature of 100 °F are 0.23 to 0.28 Btu·in/h·ft²·°F for mineral wool and fiberglass, 0.25 to 0.30 for cellular glass, 0.20 to 0.25 for polyisocyanurate and 0.25 to 0.27 for elastomeric foam. The conductivity rises with the temperature, so for a hot pipe use the value at the mean of the pipe and the outer surface. The catalog gives a table or an equation of k against the mean temperature.

How much does the insulation thickness change the loss?

The first inch of insulation cuts the loss of a bare pipe by 80 to 90 %, and each additional inch cuts less, because the surface area grows with the radius. Past the economic thickness the extra cost is not paid back by the energy saved. Compare the cost of the insulation with the yearly saving, which depends on the fuel price and on the hours of operation, to choose the thickness.

What does the calculator leave out?

The calculator uses the film coefficient that you enter for the surface, and a steady state. It does not include the heat loss at the supports, the valves and the flanges, the jacket or the wind outside, or the pipe in the ground. It also leaves out the heat lost when the system is not running. Use a thermal insulation standard, such as the ASTM C680 method, for a design with tight performance targets.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.