A masonry lintel carries a triangle of masonry over an opening, thanks to the arching action, plus any added load. The masonry lintel load calculator computes the triangular load, the bending moment, the required section modulus, the stiffness for a deflection limit and the end reactions of a steel lintel.
How the calculation works
- Enter the clear span of the opening, the weight of the wall above in pounds per square foot of wall face, and any added line load from a floor or roof that bears on the wall above the lintel.
- Enter the yield strength of the steel lintel: 36 ksi for an ordinary angle or plate, 50 ksi for a modern section.
- The calculator assumes arching action: only the masonry inside a triangle with a base equal to the span and a height of half the span loads the lintel, so W = ½ × L × (L/2) × wall weight. The triangular load has a moment of W L / 6, and the added load a moment of w L² / 8.
- It gives the required section modulus for an allowable bending stress of 0.66 Fy, the moment of inertia for a deflection of span / 600 and the end reactions.
Example
An opening has a clear span of 6 ft in a wall that weighs 80 psf, with an added line load of 300 plf and a lintel of Fy = 36 ksi. The triangle of masonry weighs ½ × 6 × 3 × 80 = 720 lb. The moment is 720 × 6 / 6 + 300 × 6² / 8 = 720 + 1,350 = 2,070 lb-ft. The required section modulus is 2,070 × 12 / 1,000 / (0.66 × 36) = 1.05 in³. The moment of inertia for a deflection of L / 600 is 3.80 in⁴, and the reaction at each end is 360 + 900 = 1,260 lb.
Why it matters
The calculator helps masons, builders, home renovators, designers and students to size the steel angle or beam that spans a window, a door or a new opening in a brick or block wall, and to see how much the arching action reduces the load. It gives the numbers to compare with the properties of a section from a table.
Good to know
Support the lintel on at least 4 in (100 mm) of bearing at each end, and use a lintel with a flange or a plate for a thick wall to avoid twisting. Keep the deflection small to avoid cracks in the masonry. Leave the wall to cure before removing any temporary shoring. Have an engineer check a lintel that carries a floor or a roof.