Three-phase voltage unbalance and motor derating calculator

Enter the three line-to-line voltages to get the average voltage, the percent unbalance, the NEMA derating factor, the extra heating and the current unbalance.

Updated on
Your inputs
V

Value out of range

V

Value out of range

V

Value out of range

Results

Voltage unbalance

1.39 %

Derate the motor and look for the cause
Average voltage
478.7 V
Motor derating factor
0.98
Extra heating of the winding
3.9 %
Estimated current unbalance
8.4 %

The three-phase voltage unbalance calculator gives the average voltage, the percent voltage unbalance by the NEMA definition, the derating factor of a motor, the extra heating of the winding and the estimated current unbalance, from the three line-to-line voltages.

How the calculation works

  • Enter the three line-to-line voltages measured at the motor terminals.
  • The calculator takes their average and the largest deviation from it.
  • It gives the voltage unbalance, the derating factor of the motor, the extra heating and the estimated current unbalance.

Example

Line voltages of 480 V, 484 V and 472 V have an average of 478.7 V. The largest deviation is 472 − 478.7 = 6.7 V, so the unbalance is 6.7 / 478.7 = 1.39 percent. The NEMA derating factor is 0.98, the extra heating of the winding is 2 × 1.39² = 3.9 percent, and the current unbalance is about 6 × 1.39 = 8.4 percent.

Why it matters

The calculator helps electricians, maintenance technicians, plant engineers and inspectors to judge a measured supply, to decide whether a motor must be derated or the supply corrected, and to explain a motor that runs hot or trips.

Good to know

Measure the three line voltages at the terminals of the motor, with the motor running at its normal load, and with the same meter for the three readings. Check the connections, the fuses and the loads on the phases before you blame the utility. Rotate the connections of the three-phase motor only with a procedure, since the rotation can change the unbalance of the current. Record the readings over a full day, because the loads of the plant change with the shifts, and compare the unbalance at the main panel with the value at the motor to find out whether the problem comes from the supply or from the branch circuit.

The three-phase power calculator gives the power of a three-phase load, the motor current calculator gives the current of a motor, the motor starting current calculator gives the inrush of a motor and the transformer fault current calculator gives the short-circuit current.

Frequently asked questions

How is the voltage unbalance computed?

The NEMA definition is the maximum deviation of a line voltage from the average of the three line voltages, divided by the average, in percent. It uses the three line-to-line voltages measured at the terminals of the motor, under load. The result shows how unequal the supply is, and not only a difference between two phases.

Why does a small unbalance matter?

A small unbalance of the voltage causes a much larger unbalance of the current, about 6 to 10 times as large, because a motor has a low impedance for the negative-sequence component. The currents heat the winding unevenly, and the temperature rise grows roughly with twice the square of the unbalance in percent. A 3.5 percent unbalance can raise the temperature of the hottest winding by 25 percent.

What is the derating factor?

The NEMA MG 1 curve gives the factor by which the horsepower of a general-purpose motor should be reduced when the unbalance is over 1 percent: about 0.95 at 2 percent, 0.88 at 3 percent, 0.82 at 4 percent and 0.75 at 5 percent. The motor should not be run above 5 percent. The ANSI C84.1 standard asks the utility to keep the unbalance under 3 percent at the meter, with no load.

What are the causes and the limits of the calculator?

The common causes are unequal single-phase loads, an open delta transformer, a blown fuse on a capacitor bank, a loose connection and an unequal tap setting. The calculator only deals with the voltage and the NEMA curve; it does not cover the phase angle unbalance, the harmonics or the motors with a special design. Measure at the motor and check the connections first.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.