Plate heat exchanger calculator: area and number of plates needed

Enter the flow and temperatures of the hot and cold sides, the heat transfer coefficient and the plate size to get the duty, the log mean temperature difference, the area and the number of plates of a plate heat exchanger.

Updated on
Your inputs
gpm

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

Btu/h·ft²·°F

Value out of range

ft²

Value out of range

Results

Heat transfer area required

76.0 ft²

Heat duty
3,000,000 Btu/h
Log mean temperature difference (counterflow)
49.33 °F
Good temperature driving force
Number of plates
23
Cold side flow rate required
75.0 gpm

The plate heat exchanger calculator finds the heat duty, the log mean temperature difference, the heat transfer area, the number of plates and the cold-side flow of a water-to-water plate exchanger from the temperatures, the flow and the overall heat transfer coefficient.

How the calculation works

  • Enter the flow rate and the inlet and outlet temperatures of the hot water. The calculator finds the heat duty from them.
  • Enter the inlet and outlet temperatures of the cold side, the overall heat transfer coefficient U of the plates (700 to 1,200 Btu/h·ft²·°F for water) and the area of one plate.
  • It computes the log mean temperature difference for counterflow, which is how plate exchangers are usually arranged.
  • It gives the heat transfer area A = Q / (U × LMTD), the number of plates and the cold-side flow rate needed to absorb the heat.

Example

Hot water at 100 gpm is cooled from 180 °F to 120 °F, so the duty is 100 × 500 × 60 = 3,000,000 Btu/h. The cold side is heated from 60 °F to 140 °F. The end differences are 180 − 140 = 40 °F and 120 − 60 = 60 °F, so the LMTD is (60 − 40) / ln(60 / 40) = 49.33 °F. With U = 800 Btu/h·ft²·°F, the area is 3,000,000 / (800 × 49.33) = 76.0 ft². With plates of 3.5 ft², this needs 23 plates, and the cold flow is 3,000,000 / (500 × 80) = 75.0 gpm.

Why it matters

The calculator helps HVAC and process engineers, district heating designers, brewers and food processors, and students to size a plate heat exchanger, to check an offer from a supplier and to see the effect of a closer approach temperature on the area and the cost. It is a quick estimate before a detailed rating by the manufacturer.

Good to know

Use a value of U from the manufacturer for the real fluids, and lower it for glycol or viscous liquids. Add a margin of 10 to 20% for fouling. Check that the two flows have a balanced heat capacity. Also check the pressure drop on both sides, as it can limit the choice of plates before the area does.

The heat exchanger LMTD calculator gives the temperature difference, the overall heat transfer coefficient calculator gives U, the specific heat calculator covers the heat of a fluid and the pump power calculator sizes the pumps for the pressure drop.

Frequently asked questions

How is the area of a plate heat exchanger computed?

The heat duty is Q = U × A × LMTD, so the area is A = Q / (U × LMTD). The duty comes from the hot side flow, its specific heat and its temperature drop. The LMTD is computed from the temperature differences at both ends of a counterflow exchanger. Plate exchangers work almost in pure counterflow, so no correction factor is needed, unlike for shell-and-tube exchangers.

Why are plate exchangers so compact?

The corrugated plates create strong turbulence even at low flow, so U for water is 3 to 5 times higher than in a shell-and-tube exchanger, from 700 to 1,200 Btu/h·ft²·°F (4,000 to 7,000 W/m²·K). The plates also stack a large area in a small volume. The close approach temperature, down to 2 °F, is possible with this design, which is useful for heat recovery.

What is the number of plates?

Each plate adds its area to the exchanger, and the two end plates do not transfer heat, so the number of plates is the area divided by the area of one plate, rounded up, plus one. The plates are arranged in passes. The final selection by the manufacturer also considers the pressure drop, the plate pattern and the gaskets, and it normally adds a margin of 10 to 20% for fouling.

What does a temperature cross mean?

A temperature cross happens when the cold outlet is hotter than the hot outlet, which a counterflow exchanger can reach, but only when the end differences stay positive. If the cold outlet is hotter than the hot inlet, or the hot outlet is colder than the cold inlet, the exchange is impossible by the second law. The calculator then gives a warning and a zero area.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.