Solar string sizing calculator: how many panels can go in series?

Enter the panel voltages, the temperature coefficient, the temperature range and the inverter limits to get the minimum and maximum panels per string.

Updated on
Your inputs
V

Value out of range

V

Value out of range

%/°C

Value out of range

°F

Value out of range

°F

Value out of range

V

Value out of range

V

Value out of range

Results

Maximum panels per string

13

Strings from the minimum to the maximum length are inside the inverter window
Minimum panels per string
5
Panel Voc at the lowest temperature
45.42 V
Panel Vmp at the highest temperature
30.31 V
Open-circuit voltage of the longest string when cold
590.5 V

A string of solar panels in series adds up voltage, and the total must fit the window of the inverter on the coldest and the hottest days. The solar PV string sizing calculator takes the panel Voc and Vmp, the temperature coefficient, the lowest and highest temperatures and the inverter limits, and gives the maximum and minimum panels per string, the cold Voc, the hot Vmp and the cold voltage of the longest string.

How the calculation works

  • Enter the panel’s Voc and Vmp from its data sheet, and the temperature coefficient of the voltage, usually about −0.25 to −0.30 percent per degree Celsius.
  • Enter the lowest ambient temperature the site will see and the highest cell temperature, which is above the air temperature on a hot day.
  • Enter the inverter’s maximum DC input voltage and its minimum MPPT voltage.
  • Voltage rises in the cold: Voc(cold) = Voc × (1 + coefficient × (T − 25 °C)). The maximum string is the inverter limit divided by that voltage, rounded down, and the minimum string is the MPPT minimum divided by the hot Vmp, rounded up.

Example

A panel has a Voc of 41.5 V, a Vmp of 34.5 V and a coefficient of −0.27 %/°C. The site sees 14 °F (−10 °C) at night and cells reach 158 °F (70 °C) in summer. The cold Voc is 41.5 × (1 + 0.0027 × 35) = 45.42 V and the hot Vmp is 34.5 × (1 − 0.0027 × 45) = 30.31 V. With an inverter that accepts 600 V and starts tracking at 150 V, the maximum string is 600 ÷ 45.42 = 13 panels, and the minimum is 150 ÷ 30.31 = 5 panels. A string of 13 panels reaches 590.5 V on the coldest morning.

Why it matters

Too many panels in a string can push the voltage above the inverter limit on a cold morning and damage it, and too few can fall under the tracking window on a hot afternoon and waste energy. Getting the string length right at the start avoids both problems and helps plan how many strings to wire in parallel.

Good to know

This is a planning estimate. Code rules, such as the voltage correction tables of the electrical code, may require different factors, and inverter data sheets list further limits like current and power. Voltage coefficients differ between Voc and Vmp, and this tool applies the same value to both. A licensed installer must confirm the design.

The solar panels calculator estimates payback, the solar battery size calculator sizes storage, the solar panel tilt calculator gives the best angle, and the wire resistance calculator checks the voltage drop in the cabling.

Frequently asked questions

Why does temperature matter for strings?

A solar panel produces a higher voltage when it is cold and a lower one when it is hot. In winter mornings, the open-circuit voltage of a string can be 10 to 20 percent above the rating on the data sheet, and it must stay below the inverter's maximum input voltage. In summer, the voltage drops and must stay above the minimum for tracking.

What is the maximum DC input voltage?

It is the highest voltage the inverter input can withstand without damage. Exceeding it can destroy the inverter and void the warranty. Residential systems commonly have limits of 500, 600 or 1,000 volts, and electrical codes also cap the voltage of the array on a roof, so check both.

What is the MPPT minimum voltage?

The maximum power point tracker of an inverter works within a voltage window. If the string voltage falls below its lower end, the inverter cannot track the power point and output drops or stops. The hot-day Vmp of a short string must therefore stay above this minimum, with some margin.

Which temperature should I use?

Use the record low air temperature for the site, as a worst case for the maximum string, and a high cell temperature, about 25 to 35 °C above the hot ambient temperature, for the minimum string. Local codes often specify the low temperature. Installers also use the manufacturer's string sizing tool, which should agree with this result.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.