The seismic story drift calculator gives the stability coefficient θ of ASCE 7, its maximum value, the P-delta amplification factor, the story drift ratio and the check against the allowable drift of the risk category.
How the calculation works
- Enter the vertical load at and above the story, the design story drift, the seismic shear and the story height.
- Enter Cd, the importance factor, β and the allowable drift of the risk category.
- The calculator gives the stability coefficient θ, its maximum, the P-delta amplification and the drift checks.
Example
A story 13 ft high (156 in) carries 9,000 kips at and above its level, with a seismic shear of 250 kips and a design story drift of 2.00 in, in a system with Cd = 4.5 and Ie = 1.0. The stability coefficient is θ = 9,000 × 2.00 × 1.0 / (250 × 156 × 4.5) = 0.103. The maximum is 0.5 / (1.0 × 4.5) = 0.111, so the ratio is 0.92. The amplification is 1 / (1 − 0.103) = 1.114. The drift is 2.00 / 156 = 1.28 %, against 2.5 % allowed, a ratio of 0.51.
Why it matters
The calculator helps structural engineers, plan checkers and students to check the second-order effects and the drift of a story after the seismic analysis, and to see how the vertical load, the shear and the stiffness change the stability.
Good to know
Use the design story drift Δ that includes Cd / Ie, not the elastic drift, and the total vertical load of the load combination of the code, which is lower than the full dead plus live load in a seismic combination. Check every story, since the lowest stories carry the most load and usually govern. If θ is over 0.10 in a story, add the amplification to the member forces of that story and the stories below.
Related tools
The shear wall calculator gives the unit shear and the hold-down force, the wind load calculator gives the lateral load of the wind, the live load reduction calculator gives the reduced live load of a column and the tuned mass damper calculator sizes a damper for a flexible structure.