The wood shear wall deflection calculator adds the bending, the shear, the nail slip and the anchor slip of the four-term equation and compares the drift with the allowable drift.
How the calculation works
- Enter the lateral load, the length and the height of the wall.
- Enter the modulus and the cross-section of the end posts, the stiffness of the sheathing, the nail slip and the anchor slip.
- The calculator gives the four terms of the deflection, the total deflection and the drift compared with the allowable drift.
Example
A wood shear wall 8 ft long and 8 ft high carries 2,600 lb, a unit shear of 325 lb/ft. The end posts have a section of 10.5 in² and a modulus of 1,600,000 psi, the sheathing has a stiffness of 14 kip/in, and the nail slip is 0.04 in and the anchor slip 0.12 in. The four terms are 0.0099 in for bending, 0.186 in for shear, 0.240 in for the nails and 0.120 in for the anchor. The total deflection is 0.556 in, a drift of 0.579 % of the height, or 0.29 of the 2 % limit.
Why it matters
The calculator helps structural engineers, framers and students to estimate how much a wood shear wall moves under a lateral load, to see which term dominates and to find out whether a longer wall, a stiffer sheathing or a better anchor is the best fix.
Good to know
Look at the largest term first. In a short, tall wall the bending and the anchor slip dominate, so use bigger end posts and a stiff hold-down anchor. In a long wall the nail slip dominates, so use closer nail spacing or thicker sheathing. Keep the anchor bolts tight and check the posts for shrinkage, and compare the drift with the limit of the wall above and the finishes.
Related tools
The shear wall hold-down calculator gives the demand and the uplift at the ends, the sheathing nail schedule calculator gives the nail count, the hurricane tie-down calculator gives the uplift force of a roof and the wood beam span calculator checks a wood beam.