COP calculator: heat pump COP, Carnot limit, second-law efficiency and cooling EER

Enter the heat delivered, the electric power and the two temperatures to get the COP, the heat taken from the source, the Carnot COP, the second-law efficiency and the cooling EER.

Updated on
Your inputs
kW

Value out of range

kW

Value out of range

°F

Value out of range

°F

Value out of range

Results

COP in heating mode

3.53

Good: at least 3 units of heat per unit of electricity
Heat taken from the source
8.60 kW
Carnot (ideal) heating COP
10.27
Second-law efficiency (actual COP / Carnot COP)
34.4 %
COP of the same machine in cooling mode
2.53
Equivalent EER in cooling mode (BTU/h per W)
8.63

The coefficient of performance (COP) is the heat moved per unit of electricity by a heat pump, an air conditioner or a refrigerator. The COP calculator gives the COP, the heat taken from the source, the Carnot limit, the second-law efficiency, the COP in cooling mode and the EER.

How the calculation works

  • Enter the heat delivered by the heat pump and the electric power that it uses, in the same unit.
  • Enter the temperature of the heat delivered (the supply water or air) and the temperature of the source (the outdoor air or the ground).
  • The calculator gives the COP = heat delivered / electric power, the heat taken from the source = heat − work, and the Carnot COP = T_hot / (T_hot − T_cold), with absolute temperatures.
  • It also gives the second-law efficiency, the COP in cooling mode (COP − 1) and the equivalent EER.

Example

A heat pump delivers 12 kW of heat with 3.4 kW of electricity, with a supply at 95 °F (35 °C) and an outdoor temperature of 41 °F (5 °C). The COP is 12 / 3.4 = 3.53 and the machine takes 8.60 kW from the outdoor air. The Carnot COP is 308.15 / 30 = 10.27, so the second-law efficiency is 34.4 %. In cooling mode the COP would be 2.53, an EER of 8.63.

Why it matters

The calculator helps homeowners, installers, students and engineers to check the performance of a heat pump from the measured heat and electric power, to compare it with the theoretical limit and to estimate the heating cost. It also shows the loss of performance that comes from a high supply temperature.

Good to know

The Carnot COP uses the temperatures of the supply and of the source only, and the real machine also has losses in the compressor, the heat exchangers and the defrost cycles. The second-law efficiency of a good heat pump is about 40 to 55 %. The cooling COP given here assumes that the same machine works in reverse with the same electric power, which is not exactly the case for a real unit.

The Carnot efficiency calculator gives the limit of heat engines, the heat pump cost calculator estimates the price of an installation, the Brayton cycle calculator handles gas turbines and the Diesel cycle calculator handles compression-ignition engines.

Frequently asked questions

What is the coefficient of performance?

The coefficient of performance, or COP, is the ratio of the useful heat delivered or removed to the work that the machine uses. A heat pump with a COP of 3.5 delivers 3.5 kWh of heat for each kWh of electricity. A COP is not an efficiency below 100 %, because the machine moves heat from a source and does not create it from the electricity alone.

What is the Carnot COP?

The Carnot COP is the highest COP that any machine can have between two temperatures. For heating it is T_hot divided by the difference T_hot − T_cold, with the temperatures in kelvin. It increases when the difference of temperature is small. This is why a heat pump works best with a low supply temperature, as in a floor heating system, and a mild outdoor temperature.

How is the cooling COP linked to the heating COP?

For the same machine, the heat delivered is the sum of the heat taken from the source and the work: Q_hot = Q_cold + W. So the heating COP is the cooling COP plus 1. The calculator subtracts 1 from the heating COP to give the COP that the machine would have if it were used to cool, assuming it has the same performance in reverse.

What is a good COP for a heat pump?

Air-source heat pumps have a seasonal COP of about 3 to 4, and ground-source units can reach 4 to 5. The COP falls when the outdoor air is colder and when the supply temperature is higher. The seasonal values are better than a single-point COP to estimate the annual cost of heating.