Heat transfer in a pipe depends on the flow regime and on the fluid. The Dittus–Boelter equation calculator gives the heat transfer coefficient of turbulent flow of water or air in a tube from its diameter, velocity and length, and for heating or cooling. It shows the Reynolds, Prandtl and Nusselt numbers and the heat transferred for a given temperature difference.
How the calculation works
- Choose the fluid (water or air), whether it is heated or cooled, and enter the diameter, velocity, length and the wall-to-fluid temperature difference.
- The calculator takes the viscosity, conductivity and Prandtl number of the fluid and finds the Reynolds number.
- The Dittus–Boelter equation is Nu = 0.023 Re^0.8 Pr^n, with n = 0.4 for heating of the fluid and n = 0.3 for cooling.
- The heat transfer coefficient is h = Nu k / D, and the heat is h × π D L × ΔT.
Example
Water at 140 °F (60 °C) is cooled in a 1 in tube at 6 ft/s, over 10 ft with a wall 20 °F colder. The Reynolds number is 97,179 and the Prandtl number is 2.99. The Nusselt number is 312, and the coefficient is 1,409 BTU/h·ft²·°F. The heat transferred over the tube is about 73,800 BTU/h.
Why it matters
The coefficient inside a tube is needed for the design of heat exchangers, boilers, condensers, cooling circuits and radiators. The Dittus–Boelter equation gives a quick value to size the tubes before a detailed calculation, and it shows how the coefficient grows with the velocity (as v^0.8).
Good to know
The calculator uses fixed properties of water and air at five temperatures, which do not change along the tube. The correlation applies to smooth tubes and turbulent flow with Re above 10,000, and it is not valid for laminar flow, for liquid metals, for very viscous liquids or for large temperature differences. For rough tubes, use a friction factor correlation such as Gnielinski’s.
Related tools
The Nusselt number calculator covers the dimensionless coefficient, the Prandtl number calculator covers the fluid property, the Reynolds number calculator covers the flow regime, and the LMTD calculator covers the use of the coefficient in a heat exchanger.