How well does a flowing fluid transfer heat in a pipe?

Choose a fluid and enter the velocity and the pipe diameter: get the Reynolds number, the Nusselt number (Dittus-Boelter) and the convection coefficient h.

Updated on
Your inputs

Value out of range

Value out of range

Results

Nusselt number

233.8

Turbulent flow: the Dittus-Boelter correlation applies
Convection coefficient h
5,505 W/(m²·K)
Convection coefficient h
969.5 BTU/(h·ft²·°F)
Reynolds number
38,555
Prandtl number
7.01

When a fluid flows past a surface, the heat it carries away depends on how vigorously it is stirred. The Nusselt number captures that: it compares heat transfer by convection with what conduction alone would give. Once you know it, the convection coefficient h follows, and with it the heat flow in a pipe or an exchanger. This calculator estimates the Nusselt number and h for flow inside a smooth circular pipe, using the Dittus-Boelter correlation.

How the calculation works

  • Reynolds number Re = velocity × diameter ÷ kinematic viscosity
  • Turbulent flow (Re above 2,300): Nu = 0.023 × Re^0.8 × Pr^n, with n = 0.4 for heating and 0.3 for cooling
  • Laminar flow (Re below 2,300): Nu = 3.66
  • Convection coefficient h = Nu × k ÷ D, where k is the thermal conductivity of the fluid

Example

Water at 20 °C flows at 5 ft/s (1.52 m/s) in a pipe with an inside diameter of 1 inch (25.4 mm) and is heated. The Reynolds number is about 38,600, which means turbulent flow. With a Prandtl number of 7.01, the Nusselt number is about 234 and the convection coefficient is about 5,500 W/(m²·K), around 970 BTU/(h·ft²·°F).

Why it matters

The coefficient h sets the size of heat exchangers, boilers, radiators and cooling channels. Raising the velocity increases Re and h, but it also raises pumping power, so designers look for a balance. Air has a far lower conductivity than water, which is why gas-side heat transfer is usually the bottleneck in a heat exchanger.

Good to know

The correlation is for smooth pipes and moderate temperature differences between the wall and the fluid. Fluid properties change with temperature, so use values near the mean temperature of the fluid. Rough pipes, curved pipes, non-circular ducts and very viscous liquids need other correlations. The result is typically accurate to within about 15-25%.

The Reynolds number calculator gives the flow regime, the heat exchanger LMTD calculator sizes an exchanger, and the heat conduction calculator handles heat flow through a solid wall.

Frequently asked questions

What is the Nusselt number?

A dimensionless number that compares heat transfer by convection with pure conduction in the fluid: Nu = h × D ÷ k. A Nusselt number of 1 means no convection at all; values in the hundreds mean heat is carried very effectively by the moving fluid.

What is the Dittus-Boelter equation?

A correlation for turbulent flow in a smooth pipe: Nu = 0.023 × Re^0.8 × Pr^n, with n = 0.4 when the fluid is heated and 0.3 when it is cooled. It is valid for Re above about 10,000 and Prandtl numbers from 0.6 to 160.

Why is the laminar value constant?

In fully developed laminar flow in a long circular pipe, the heat transfer coefficient depends only on the geometry. It does not depend on the velocity, and the Nusselt number is 3.66 for a constant wall temperature or 4.36 for a constant heat flux.

What about the entrance region?

Near the pipe entrance, the boundary layer is thin and heat transfer is higher. For short pipes, the correlation underestimates h, and entrance corrections are applied.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.