When a fluid flows past a surface, the heat it carries away depends on how vigorously it is stirred. The Nusselt number captures that: it compares heat transfer by convection with what conduction alone would give. Once you know it, the convection coefficient h follows, and with it the heat flow in a pipe or an exchanger. This calculator estimates the Nusselt number and h for flow inside a smooth circular pipe, using the Dittus-Boelter correlation.
How the calculation works
- Reynolds number Re = velocity × diameter ÷ kinematic viscosity
- Turbulent flow (Re above 2,300): Nu = 0.023 × Re^0.8 × Pr^n, with n = 0.4 for heating and 0.3 for cooling
- Laminar flow (Re below 2,300): Nu = 3.66
- Convection coefficient h = Nu × k ÷ D, where k is the thermal conductivity of the fluid
Example
Water at 20 °C flows at 5 ft/s (1.52 m/s) in a pipe with an inside diameter of 1 inch (25.4 mm) and is heated. The Reynolds number is about 38,600, which means turbulent flow. With a Prandtl number of 7.01, the Nusselt number is about 234 and the convection coefficient is about 5,500 W/(m²·K), around 970 BTU/(h·ft²·°F).
Why it matters
The coefficient h sets the size of heat exchangers, boilers, radiators and cooling channels. Raising the velocity increases Re and h, but it also raises pumping power, so designers look for a balance. Air has a far lower conductivity than water, which is why gas-side heat transfer is usually the bottleneck in a heat exchanger.
Good to know
The correlation is for smooth pipes and moderate temperature differences between the wall and the fluid. Fluid properties change with temperature, so use values near the mean temperature of the fluid. Rough pipes, curved pipes, non-circular ducts and very viscous liquids need other correlations. The result is typically accurate to within about 15-25%.