Flash steam calculator: flash steam fraction of high pressure condensate

Enter the condensate flow and the pressures before and after the letdown valve to get the saturation temperatures, the flash steam fraction, the flash steam flow and the condensate left in the flash tank.

Updated on
Your inputs
lb/h

Value out of range

psig

Value out of range

psig

Value out of range

Results

Flash steam fraction

11.90 %

Saturation temperature before the valve
338.4 °F
Saturation temperature of the flash tank
227.1 °F
Flash steam flow
119.0 lb/h
Condensate left in the tank
881.0 lb/h

Hot condensate that drops to a lower pressure boils again and makes flash steam. The flash steam calculator gives the saturation temperatures, the flash steam fraction, the flash steam flow and the condensate left from the flow and the pressures before and after the letdown valve.

How the calculation works

  • Enter the condensate flow in lb/h from the steam traps or the process, and the pressure of the condensate just before the letdown valve.
  • Enter the pressure of the flash tank or the return line, where the condensate expands.
  • The calculator finds the saturation temperature at each pressure, then the heat that the hot condensate loses when it cools down to the lower saturation temperature.
  • That heat becomes the latent heat of the flash steam. The fraction is (hf1 − hf2) / hfg2, and the calculator gives the flash steam flow and the condensate left.

Example

A flow of 1,000 lb/h of condensate at 100 psig (338.4 °F) goes to a flash tank at 5 psig (227.1 °F). The liquid enthalpy falls from 309.6 to 195.3 Btu/lb, and the latent heat at the tank is 960.8 Btu/lb. The flash steam fraction is (309.6 − 195.3) / 960.8 = 11.9%. The flash steam flow is 119 lb/h, and 881 lb/h of condensate stays in the tank.

Why it matters

The calculator helps plant engineers, boiler operators, energy auditors and students to see how much steam can be recovered from the condensate, to size a flash tank and to find the savings of a heat recovery project. It shows why the high-pressure condensate is a valuable resource.

Good to know

Use the real pressures at the valve and in the tank. Remember that the quantity of flash steam grows quickly with the pressure drop. Size the flash tank for the steam velocity, and check that the low-pressure steam has a user. Do not vent the flash steam to the atmosphere if you can recover it.

The latent heat calculator covers the phase change, the specific heat calculator gives the heat content of water, the boiler size calculator sizes the boiler and the heat of combustion calculator gives the energy of the fuel.

Frequently asked questions

What is flash steam?

When hot condensate at a high pressure drops to a lower pressure, its temperature is above the boiling point at the new pressure. A part of the liquid boils off at once, with no extra heat, which makes steam. This steam is called flash steam. It is at the lower pressure, and it can be used in a low-pressure line, to heat air or water or a process, instead of being lost to the atmosphere.

How is the flash fraction computed?

The excess heat of the condensate is the difference of its enthalpy between the high pressure and the low pressure, hf1 − hf2. This heat evaporates a part of the liquid, which needs the latent heat hfg2 per unit of mass at the low pressure. So the fraction that flashes is x = (hf1 − hf2) / hfg2. The higher the pressure before the valve and the lower the pressure after it, the larger the fraction.

How can flash steam be used?

A flash tank separates the steam from the liquid, and sends the steam to a low-pressure user such as a heating coil, a feedwater heater, a deaerator or a space heating system. The remaining condensate is returned to the boiler feed. This saves fuel and water treatment, and it avoids the plume of steam at the vent. Size the flash tank so that the steam velocity is low, to avoid carrying liquid droplets.

What are the limits of this calculator?

The enthalpies and the saturation temperature are computed with approximations that are valid from about 212 °F to 390 °F (100 °C to 200 °C), with an error of about 1% on the flash fraction. For a precise result, use the steam tables. The calculator assumes pure condensate, an adiabatic letdown and a flash tank at a steady pressure, and it does not include the heat loss of the tank or the steam leaking through traps.

Was this calculator helpful?