Cooling load sensible estimate calculator

Enter the envelope, the glass, the people, the lights, the equipment and the ventilation to get each gain, the total sensible load, the total cooling load and the tons.

Updated on
Your inputs
BTU/h·°F

Value out of range

°F

Value out of range

°F

Value out of range

ft²

Value out of range

Value out of range

BTU/h·ft²

Value out of range

Value out of range

W

Value out of range

W

Value out of range

cfm

Value out of range

Value out of range

Results

Total cooling load with latent

55,926 BTU/h

Conduction through the envelope
7,000 BTU/h
Solar gain through the windows
7,200 BTU/h
Internal gains: people, lights, equipment
23,425 BTU/h
Ventilation air, sensible
4,320 BTU/h
Total sensible load
41,945 BTU/h
Cooling capacity in tons
4.66 tons

The cooling load estimate calculator gives the conduction, the solar gain, the internal gains and the ventilation load of a space, the total sensible load, the total cooling load with the latent part and the tons of cooling, from the envelope, the glass, the occupancy and the airflow.

How the calculation works

  • Enter the conduction UA of the envelope, the outdoor and indoor temperatures and the window data.
  • Enter the people, the lighting and equipment power, the ventilation airflow and the sensible heat ratio.
  • The calculator finds each sensible gain, the total sensible load, the total load with the latent part and the tons of cooling.

Example

A room with an envelope UA of 350 BTU/h·°F and a design difference of 20 °F gains 7,000 BTU/h by conduction. 120 ft² of glass with a coefficient of 0.4 and 150 BTU/h·ft² gain 7,200 BTU/h. 20 people (5,000), 2,400 W of lights (8,189) and 3,000 W of equipment (10,236) give 23,425 BTU/h, and 200 cfm of ventilation give 1.08 × 200 × 20 = 4,320 BTU/h. The sensible load is 41,945 BTU/h, and with a sensible heat ratio of 0.75 the total is 55,926 BTU/h, that is 4.66 tons.

Why it matters

The calculator helps HVAC designers, contractors, building owners and homeowners to make a first estimate of the size of an air conditioner for an office, a shop or a room, to see which gain is the largest, and to compare the effect of the glass, the lighting and the ventilation.

Good to know

Use the real outdoor design temperature of your location (the 1 percent value of ASHRAE) and an indoor temperature of 75 °F. Take the UA from the areas and the U-values of the walls, the roof and the windows. Reduce the lighting and equipment power if they are not on at the peak, and do not oversize the unit, since a large unit cycles on and off and does not remove the humidity.

The heat loss calculator gives the winter loss of a building, the sensible heat ratio calculator gives the share of the sensible load, the window solar heat gain calculator gives the solar load of a window and the air changes calculator gives the ventilation airflow.

Frequently asked questions

What does the estimate include?

The estimate adds the main sensible gains of a space at the design hour: the conduction through the walls, the roof and the windows, the solar gain through the glass, the heat of the people, the lights and the equipment, and the sensible heat of the ventilation air. The sum is divided by the sensible heat ratio to get the total, with the latent load of the people and the humid ventilation air.

Where do the factors come from?

The sensible heat of a seated person at light work is about 250 BTU/h, and 1 W of electricity gives 3.412 BTU/h. The sensible heat of the ventilation air is 1.08 times the cfm times the temperature difference in °F, where 1.08 comes from the density and the specific heat of air. The solar gain of the glass is the area times the coefficient times the peak solar heat gain of the orientation, which you enter.

How good is the result?

This is a first estimate for early sizing, and it takes all the gains at the same time at the peak, which is conservative. A load calculation by the ASHRAE method or the ACCA Manual J includes the time lag of the heat stored in the walls, the orientation of each surface, the shading, the infiltration and the diversity of the loads, and it often gives a lower total. Do not use it for the final equipment selection.

What does the calculator leave out?

The calculator does not include the roof and wall solar effect separately, the infiltration, the duct gains, the pull-down load, the safety factor or the diversity of the people and the lighting. Add the sunlit roof and walls to the UA with an equivalent temperature difference when it matters. Use the result with a margin of 10 percent, and check the humidity control of the unit.