Curtain wall mullion deflection calculator

Enter the wind pressure, the mullion spacing, the span, the inertia and the modulus to get the line load, the deflection, the allowable deflection and the inertia needed.

Updated on
Your inputs
psf

Value out of range

ft

Value out of range

ft

Value out of range

in⁴

Value out of range

ksi

Value out of range

Value out of range

Results

Deflection to allowable ratio

0.88

The deflection is within the limit
Wind line load on the mullion
125 lb/ft
Maximum deflection
0.722 in
Allowable deflection
0.823 in
Moment of inertia needed for the limit
7.02 in⁴

The curtain wall mullion calculator gives the wind line load, the maximum deflection of a simple span, the allowable deflection for the limit you choose, the ratio and the moment of inertia needed, from the wind pressure, the spacing, the span, the inertia and the modulus.

How the calculation works

  • Enter the wind pressure, the tributary width (the mullion spacing) and the span between anchors.
  • Enter the moment of inertia and the modulus of elasticity of the mullion, and the deflection limit as a span divided by a number.
  • The calculator gives the line load, the maximum deflection, the allowable deflection and the inertia needed.

Example

An aluminum mullion with 8.0 in⁴ spans 12 ft between anchors, with a spacing of 5 ft and a wind pressure of 25 psf. The line load is 25 × 5 = 125 lb/ft. The deflection of a simple beam is 5 w L⁴ / (384 E I) = 0.722 in. The limit L/175 is 144 / 175 = 0.823 in, so the ratio is 0.88 and the inertia needed for the limit is 7.02 in⁴.

Why it matters

The calculator helps facade engineers, curtain wall designers, glaziers and architects to check quickly if a mullion section is stiff enough for the wind, to compare spacings and spans, and to find the inertia to ask of the manufacturer.

Good to know

Use the design wind pressure for the corner or the edge zone of the facade, not only the field value, since the zones near the corners can have a pressure that is twice as high. Check the deflection under the service wind pressure that the specification names, which can be lower than the strength wind pressure. Remember that the deflection limit of the glass edge is often the one that governs, and ask for the inertia with the mullion cover and the reinforcement considered.

The wind cladding pressure calculator gives the pressure on the zones of the facade, the wind load calculator gives the load of the wind on a surface, the beam deflection calculator checks a simple beam and the two-span continuous beam calculator checks a continuous mullion.

Frequently asked questions

What deflection limit applies to a mullion?

The usual limit of the aluminum curtain wall industry is L/175 of the span for the wind load, with a maximum of 3/4 in for a span over 13.5 ft where the limit is L/240 plus 1/4 in. Glass of a large panel can ask for L/175 or 3/4 in as a maximum, whichever is smaller. The project specification and the glazing maker may ask for more, such as L/240 or L/360 for a stone or a brittle cladding.

How is the line load found?

The wind pressure acts on the cladding and on the glass, and each mullion carries the strip of the wall that is half the spacing to the left and half to the right. The line load of the mullion is the pressure times this tributary width. The calculator takes a uniform load on a simple span, which is slightly conservative for a mullion that is continuous over two or more spans, and unconservative for the span of a continuous mullion at the end.

What is the effect of the span and the inertia?

The deflection grows with the fourth power of the span and falls with the inertia in proportion. A mullion that is 10 % longer deflects 46 % more, and one with a 20 % higher inertia deflects 17 % less. The span is therefore the best way to control the deflection, and a stack joint or an added anchor can help more than a deeper section.

What does the calculator leave out?

The calculator does not check the bending stress, the shear, the deflection of the glass edge, the combined load with the dead load of the glass, the movement of the slab or the thermal bowing of the section. It also takes a constant inertia, while the real mullion may have a splice sleeve. Use the data of the manufacturer for the structural check and for the wind pressure of the code of your site.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.