Hydrant flow test calculator: tested flow and available fire flow at a residual pressure

Enter the static, residual and Pitot pressures, the outlet diameter and coefficient and the required residual pressure to get the tested flow, the pressure drop and the flow available at the required residual pressure.

Updated on
Your inputs
psi

Value out of range

psi

Value out of range

psi

Value out of range

psi

Value out of range

Results

Flow available at the required residual pressure

1,701 gpm

Flow measured at the test
888 gpm
Pressure drop during the test
21.4 %
The drop is large enough for a reliable extrapolation

The hydrant flow test calculator gives the flow of a hydrant from the Pitot pressure and the outlet, the pressure drop of the test and the flow available at a required residual pressure, usually 20 psi, by the 0.54 power extrapolation of NFPA 291.

How the calculation works

  • Enter the static pressure read at a hydrant before the flow, and the residual pressure read at the same hydrant while another hydrant flows.
  • Enter the Pitot pressure at the flowing outlet, its diameter and its coefficient.
  • Enter the residual pressure that you want to guarantee, usually 20 psi for fire protection.
  • The calculator finds the flow measured in the test, the pressure drop and the flow available at the required residual pressure with the 0.54 power extrapolation.

Example

The static pressure is 70 psi and drops to 55 psi while a 2.5 in smooth outlet (c = 0.9) flows with a Pitot reading of 28 psi. The flow is 29.83 × 0.9 × 2.5² × √28 = 888 gpm. The pressure drop is 15 / 70 = 21.4%, enough for a reliable test. At 20 psi of residual pressure the available flow is 888 × ((70 − 20) / (70 − 55))^0.54 = 1,701 gpm.

Why it matters

The calculator helps fire protection engineers, sprinkler designers, water utility staff, fire departments and students to process the data of a flow test, to check that the supply of a building is enough for the required fire flow and to size a fire pump. It gives the available flow in seconds from the three readings of the test.

Good to know

Open enough outlets to cause a pressure drop of at least 10 to 25%, read the gauges at the same time and note the date and the hour of the test. Use the test of the last 12 months for a design. Apply a margin to the available flow, and do not extrapolate to a residual pressure that is very low compared with the one of the test.

The needed fire flow calculator gives the flow required for a building, the friction loss calculator gives the pressure losses in the pipes, the sprinkler system demand calculator gives the demand of the sprinklers and the pump power calculator sizes the fire pump.

Frequently asked questions

What is a hydrant flow test?

A hydrant flow test measures what a water main can supply in a fire. Water is flowed from one hydrant while the pressure is read at a second hydrant, the residual hydrant, and the flow is found with a Pitot gauge at the first. The test gives the static pressure, the residual pressure and the flow, which are the three data needed to find the available flow at any residual pressure and to design a sprinkler system or a fire pump.

How is the flow computed from the Pitot pressure?

The flow of an outlet is Q = 29.83 c d² √P, where d is the diameter of the outlet in inches, P the Pitot pressure in psi and c the coefficient of the outlet, 0.9 for a smooth and rounded outlet, 0.8 for a square one and 0.7 for an outlet that projects into the barrel. The coefficient comes from the shape of the opening and reduces the theoretical flow.

How is the available flow found?

The relation between the flow and the pressure drop in the main follows a power law, Q ∝ ΔP^0.54, as in the Hazen-Williams formula. The flow at a residual pressure Pr₂ is therefore Q₂ = Q₁ ((Ps − Pr₂) / (Ps − Pr₁))^0.54. The extrapolation is reliable when the pressure drop in the test is at least 10% of the static pressure, because a very small drop amplifies the errors.

What are the limits of the calculator?

The calculator uses the standard formulas of NFPA 291. The results depend on the accuracy of the gauges, on the condition of the valves in the network and on the demand at the time of the test, which changes during the day. An available flow far beyond the flow of the test should be used with caution. A flow test must be carried out and approved by the water utility or a qualified person.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.