Stairwell pressurization airflow calculator: how much air must the pressurization fan supply?

Enter the number of doors, the doors open, the door size, the gap, the pressure difference and the open door velocity to get the leakage of the closed doors, the flow through the open doors and the total supply airflow.

Updated on
Your inputs

Value out of range

Value out of range

ft

Value out of range

ft

Value out of range

in

Value out of range

in. w.c.

Value out of range

ft/min

Value out of range

Results

Total supply airflow of the stairwell

5,885 cfm

Leakage through one closed door
211 cfm
Leakage through all the closed doors
1,685 cfm
Airflow through the open doors
4,200 cfm

The stairwell pressurization airflow calculator gives the air that a pressurization fan must supply to a stairwell, from the leakage of the closed doors at the design pressure difference and the flow through the open doors, for a smoke control system.

How the calculation works

  • Enter the number of doors that open to the stairwell and the number of them that are open at the same time, for example the door at the discharge level and the one at the fire floor.
  • Enter the size of a door and the average gap around a closed door.
  • Enter the design pressure difference between the stairwell and the building, and the air velocity through an open door.
  • The calculator finds the leakage of a closed door, of all the closed doors, the flow through the open doors and the total supply airflow of the pressurization fan.

Example

A stairwell has 10 doors of 3 ft by 7 ft with a gap of 0.125 in, and 2 doors are open. The leakage area of a closed door is 2 × (3 + 7) × 0.125 / 12 = 0.208 ft², and its leakage is 2,610 × 0.208 × √0.15 = 211 cfm at 0.15 in. w.c. The 8 closed doors leak 1,685 cfm. The 2 open doors pass 2 × 3 × 7 × 100 = 4,200 cfm at 100 ft/min. The total supply is 5,885 cfm.

Why it matters

The calculator helps fire protection and mechanical engineers, building designers and fire marshals to estimate the size of a stairwell pressurization fan in a first design, to see the effect of the number of doors and of the gap, and to compare design assumptions. It shows that the open doors dominate the airflow.

Good to know

Use the real gap of the doors and the number of doors open at the same time required by the code, and add a safety margin. Provide a relief of the excess pressure so that the doors can still be opened, with a force below the limit of the code, and test the system on site. Coordinate the system with the fire alarm and the HVAC.

The needed fire flow calculator gives the water supply for a building, the duct size calculator sizes the supply duct, the air changes calculator gives ventilation rates and the sprinkler system demand calculator gives the water demand of the sprinklers.

Frequently asked questions

What is stairwell pressurization?

A stairwell pressurization system is a smoke control system in which a fan supplies outdoor air to the stairwell, so that its pressure is higher than that of the floors. The smoke of a fire on a floor then cannot enter the stairwell when a door is closed, and with an open door the airflow through the opening keeps the smoke out. The stairwell stays a safe route for the occupants and for the firefighters.

How is the leakage of a closed door found?

The air that leaks around a closed door follows the orifice equation, Q = C A √ΔP. In US units the airflow in cfm is 2,610 A √ΔP, with the leakage area A in ft² and the pressure difference ΔP in inches of water. The leakage area is the gap multiplied by the perimeter of the door. The design pressure difference is usually between 0.10 and 0.35 in. w.c., or 25 to 87 Pa, and is limited so that the doors can still be opened.

Why must the open doors be included?

When people leave the building, one or more doors are open, for instance the door at the discharge level and the one of the fire floor. The airflow through an open door must reach a minimum velocity, usually 100 ft/min (0.5 m/s), to stop the smoke from entering the stairwell. This flow is much larger than the leakage of the closed doors, and it governs the size of the fan.

What are the limits of the calculator?

The calculator gives the supply airflow for the design conditions and does not include the leakage of the stairwell walls, the shaft and the elevator, the stack effect, the wind, the relief of the excess pressure, or the control of the pressure when the doors open and close. The design of a smoke control system follows NFPA 92 and the local code, and must be made and tested by a qualified engineer.