Floor walking vibration peak acceleration calculator

Enter the natural frequency, the effective weight, the damping and the use of the floor to get the peak acceleration from walking, the ratio to the limit and the weight needed.

Updated on
Your inputs
Hz

Value out of range

lb

Value out of range

Results

Peak acceleration

0.44 % g

Acceptance limit
0.5 % g
Ratio of the acceleration to the limit
0.88
Acceptable for walking vibration
Effective weight needed for the limit
26,351 lb

The floor walking vibration calculator gives the peak acceleration caused by walking on a floor, the ratio to the acceptance limit and the effective weight needed to meet it, from the natural frequency, the effective weight, the damping and the use of the floor.

How the calculation works

  • Enter the natural frequency and the effective weight of the floor panel.
  • Choose the damping ratio and the acceptance limit for the use of the floor.
  • The calculator finds the peak acceleration from walking, the ratio to the limit and the effective weight needed to meet the limit.

Example

A floor with a natural frequency of 8 Hz, an effective weight of 30,000 lb and a damping of 3 percent has a peak acceleration of 65 × e^(−0.35 × 8) / (0.03 × 30,000) = 0.44 percent of g. For an office the limit is 0.5 percent, so the ratio is 0.88 and the floor is acceptable. To reach the limit the floor needs an effective weight of at least 26,351 lb.

Why it matters

The calculator helps structural engineers, floor designers, architects and students to check the walking comfort of a steel or concrete floor in the early design, to see the effect of the damping and the weight, and to decide whether to stiffen the floor.

Good to know

Raise the frequency of the floor above 8 Hz when you can, since it has the largest effect. Add stiffness to the beams and the girders, use a thicker slab, and count the non-structural partitions in the damping only if they will stay in place. Compute the frequency with the floor natural frequency calculator, then use this value here, and ask for a full analysis if the ratio is over 0.8.

The floor natural frequency calculator gives the frequency of a floor panel, the floor load calculator gives the loads of a floor, the vibration isolation calculator sizes the mounts of a machine and the tuned mass damper calculator sizes a damper for a structure.

Frequently asked questions

What is the equation of the peak acceleration?

The design guide 11 of the AISC and the CISC gives the peak acceleration from walking as a_p / g = P0 e^(−0.35 fn) / (β W), where P0 is a constant force of 65 lb for floors and 92 lb for footbridges, fn is the natural frequency of the floor, β is the damping ratio and W is the effective weight of the panel. The acceleration falls fast when the frequency rises, and it falls when the weight or the damping grows.

What is the effective weight?

The effective weight W is the weight of the part of the floor that vibrates with the beam or girder panel that you study, including the dead load and the part of the live load that is present in normal use, which is about 10 to 25 percent of the design live load for an office. The calculator takes it as an input, and it comes from the width of the effective slab and the length of the panel of the structure.

What are the acceptance limits?

The limits for the peak acceleration are 0.5 percent of g for offices, residences and churches, 1.5 percent for shopping malls, 2.5 percent for indoor footbridges and 5 percent for outdoor footbridges. A laboratory or an operating room has much smaller limits, set by the equipment. The more people are sensitive to the movement, the lower the limit.

What does the calculator leave out?

The calculator uses the closed-form equation of the guide and gives an estimate of the walking response. It does not include the rhythmic activities such as dancing and aerobics, the response of sensitive equipment, the effect of the support conditions or the higher harmonics of the walking, and the equation is made for floors with a frequency of 3 to 10 Hz. Use a full dynamic analysis for a special floor.