One-way slab minimum thickness calculator: thickness that avoids a deflection calculation (ACI 318)

Enter the span, the member and support condition and the steel yield strength to get the minimum thickness of a one-way slab or beam, a practical thickness rounded up and the self-weight.

Updated on
Your inputs
ft

Value out of range

ksi

Value out of range

Results

Practical thickness rounded up to 1/2 in

7.0 in

Modification factor for the steel yield strength
1.00
Minimum thickness without deflection calculation
6.86 in
Self-weight of the practical thickness
87.5 psf
Span-to-depth ratio of the practical thickness
27.4

The one-way slab minimum thickness calculator gives the minimum thickness of a non-prestressed one-way slab or beam from its span and support condition in ACI 318, below which a deflection calculation is required, with the correction for the yield strength of the steel.

How the calculation works

  • Enter the span length of the slab or beam.
  • Choose the member (slab or beam) and its support condition: simply supported, one end continuous, both ends continuous or cantilever.
  • Enter the yield strength of the reinforcement. The table applies to Grade 60 steel, and other grades use the factor (0.4 + fy / 100).
  • The calculator gives the minimum thickness of ACI 318 below which a deflection calculation is required, a practical thickness and its self-weight.

Example

A one-way slab spans 16 ft and is continuous at both ends, with Grade 60 steel (fy = 60 ksi). The table gives L/28, and the factor is 0.4 + 60 / 100 = 1.00. The minimum thickness is 16 × 12 / 28 × 1.00 = 6.86 in. Rounded up to the next half inch, the practical thickness is 7.0 in. The self-weight is 7 × 150 / 12 = 87.5 psf and the span-to-depth ratio is 192 / 7 = 27.4.

Why it matters

The calculator helps structural engineers, builders, architects and students to make a first choice of the depth of slabs and beams, to estimate the concrete quantities and the self-weight and to avoid the deflection calculation when it is not needed. It is a quick tool for the preliminary design of a floor system.

Good to know

Use the span from face to face or the clear span plus the depth, as defined by the code, and take the support condition for the member considered. Round up to the next practical thickness. Check the shear, the flexure, the fire rating, the cover and the vibration. If there are brittle partitions or a long-term deflection concern, calculate the deflection even if the member satisfies the table.

The beam deflection calculator checks deflections, the concrete volume calculator gives the quantity of concrete, the concrete crack width calculator checks cracks and the stirrup spacing calculator covers shear reinforcement.

Frequently asked questions

What is the minimum thickness rule?

ACI 318 gives minimum thicknesses of non-prestressed one-way slabs and beams as fractions of the span: L/20 if simply supported, L/24 with one end continuous, L/28 with both ends continuous and L/10 for a cantilever slab. For beams the denominators are 16, 18.5, 21 and 8. If the member is at least this thick, the deflection calculation is not required, because the rule is designed to keep the deflection within the limits.

When does the rule not apply?

The table is for members that do not support or are not attached to partitions or other construction likely to be damaged by large deflections. When they do, the deflection must be calculated, whatever the thickness. The table is also for normal-weight concrete, and for lightweight concrete the minimum thickness is increased by a factor. Prestressed and two-way slabs follow other rules.

Why is there a factor for the steel yield strength?

The tabulated values are for Grade 60 reinforcement. For another yield strength fy, the minimum thickness is multiplied by 0.4 + fy / 100,000 psi, which is 0.4 + fy / 700 with fy in MPa. A higher-strength steel works at a higher stress, so it causes higher curvature and deflection under the same load, and the thickness must be higher. A lower strength allows a smaller thickness.

Is the minimum thickness the design thickness?

No. It is the thickness below which a check of the deflection is required, and it does not ensure that the slab has enough flexural strength or shear strength, or a good fire rating and cover. The final thickness is set by the strength design, and usually rounded to a practical value and to the formwork. Using the minimum can save concrete, but a thicker slab is stiffer and is often better for vibration.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.