Standpipe demand flow and pressure calculator for a building

Enter the number of standpipes, the sprinklers, the height, the residual pressure and the friction loss to get the demand flow, the flow per standpipe and the pressure required at the base.

Updated on
Your inputs

Value out of range

ft

Value out of range

psi

Value out of range

psi

Value out of range

Results

Pressure required at the base

164.0 psi

The pressure can be supplied by a single zone and a standard fire pump
Demand flow of the system
1,000 gpm
Average flow per standpipe
333 gpm
Pressure of the elevation
52.0 psi

The standpipe demand flow and pressure calculator gives the demand flow, the flow per standpipe, the pressure of the elevation and the pressure required at the base of a fire standpipe system, from the number of standpipes, the height and the residual pressure.

How the calculation works

  • Enter the number of standpipes and say if the building is sprinklered.
  • Enter the height of the highest hose connection, the residual pressure required there and the friction loss.
  • The calculator finds the demand flow, the flow per standpipe, the pressure of the elevation and the pressure required at the base.

Example

A sprinklered building has 3 standpipes. The demand is 500 + 250 × 2 = 1,000 gpm, which is also the limit for a sprinklered building, so the average flow is 333 gpm per standpipe. The highest connection is at 120 ft, so the elevation takes 0.433 × 120 = 52.0 psi. With 100 psi of residual pressure and 12 psi of friction, the pressure required at the base is 100 + 52.0 + 12 = 164.0 psi.

Why it matters

The calculator helps fire protection engineers, mechanical contractors, building designers and students to see the order of magnitude of the flow and of the pressure of a standpipe system, to check if a fire pump is needed, and to compare the effect of the height and of the number of standpipes.

Good to know

Remember that the pressure of the elevation is the largest part of the pressure in a tall building, and that a pressure above about 175 psi needs pressure zones or pressure-reducing valves. Test the system with the pressure and the flow at the highest outlet before the occupancy, and keep the hose connections clear and marked on each floor.

The hydrostatic test pressure calculator gives the test pressure of the piping, the water main flushing time and volume calculator plans the flushing of the pipes, the NPSH calculator checks the suction of a pump and the pipe support spacing calculator checks the supports of the pipes.

Frequently asked questions

What is a standpipe?

A standpipe is a vertical pipe that goes up in a building, usually in a stairwell, with a hose connection at each floor. The firefighters connect their hoses to it and do not need to pull the hoses from the street up the stairs. The pipe can be wet, which means that it is always full of water, or dry, which means that the fire department supplies it through a connection at the street.

How is the demand flow found?

In the usual rules of the standards, the first standpipe is designed for 500 gpm, and each additional standpipe adds 250 gpm. The total is limited to 1,250 gpm, or to 1,000 gpm if the building is fully sprinklered. The flow is the one needed for the hose streams of the fire department, and it is the sum of the flows of the standpipes that can be used at the same time.

Why is the pressure at the base so high?

The pressure at the base must give the residual pressure at the highest hose connection, usually 100 psi at the outlet of the hose valve, and it must also carry the water up the building. Each foot of height needs 0.433 psi, so a 120 ft building takes 52 psi only for the elevation. The friction loss in the pipe and in the valves, which grows with the square of the flow, is added to it.

What are the limits of the calculator?

The calculator gives a first estimate with a fixed friction loss and the simple rules of flow. It does not calculate the friction of the real piping with the Hazen-Williams equation, nor the pressure-reducing valves of a high-rise, the pressure of the sprinklers on the same riser, the water supply of the city or the size of the fire pump and of the tanks. The design must follow the standard and the authority having jurisdiction.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.