The standpipe demand flow and pressure calculator gives the demand flow, the flow per standpipe, the pressure of the elevation and the pressure required at the base of a fire standpipe system, from the number of standpipes, the height and the residual pressure.
How the calculation works
- Enter the number of standpipes and say if the building is sprinklered.
- Enter the height of the highest hose connection, the residual pressure required there and the friction loss.
- The calculator finds the demand flow, the flow per standpipe, the pressure of the elevation and the pressure required at the base.
Example
A sprinklered building has 3 standpipes. The demand is 500 + 250 × 2 = 1,000 gpm, which is also the limit for a sprinklered building, so the average flow is 333 gpm per standpipe. The highest connection is at 120 ft, so the elevation takes 0.433 × 120 = 52.0 psi. With 100 psi of residual pressure and 12 psi of friction, the pressure required at the base is 100 + 52.0 + 12 = 164.0 psi.
Why it matters
The calculator helps fire protection engineers, mechanical contractors, building designers and students to see the order of magnitude of the flow and of the pressure of a standpipe system, to check if a fire pump is needed, and to compare the effect of the height and of the number of standpipes.
Good to know
Remember that the pressure of the elevation is the largest part of the pressure in a tall building, and that a pressure above about 175 psi needs pressure zones or pressure-reducing valves. Test the system with the pressure and the flow at the highest outlet before the occupancy, and keep the hose connections clear and marked on each floor.
Related tools
The hydrostatic test pressure calculator gives the test pressure of the piping, the water main flushing time and volume calculator plans the flushing of the pipes, the NPSH calculator checks the suction of a pump and the pipe support spacing calculator checks the supports of the pipes.