Water main flushing calculator: flow needed, time and water to discharge

Enter the pipe diameter and length, the flushing velocity, the volume changes and the hydrant flow to get the flow needed, the pipe volume, the flushing time and the water to discharge.

Updated on
Your inputs
in

Value out of range

ft

Value out of range

ft/s

Value out of range

Value out of range

gpm

Value out of range

Results

Flow needed

881 gpm

Volume of the pipe
11,750 gal
Flushing time
40.0 min
Total water to discharge
35,251 gal
Ratio of the needed flow to the available flow
0.88
The hydrant gives enough flow

The water main flushing calculator gives the flow needed, the pipe volume, the flushing time, the total water to discharge and the ratio to the available flow for a new water main, from the diameter, the length, the flushing velocity and the number of volume changes.

How the calculation works

  • Enter the inside diameter and the length of the pipe to flush.
  • Enter the flushing velocity, the number of pipe volume changes and the flow available at the hydrant.
  • The calculator finds the flow needed, the pipe volume, the flushing time, the total water and the ratio to the available flow.

Example

A 12 in main has a section of 0.785 ft². At 2.5 ft/s, the flow needed is 2.5 × 0.785 × 448.8 = 881 gpm. The 2,000 ft of pipe hold 11,750 gal. For 3 volume changes, the flushing takes 3 × 2,000 / 2.5 / 60 = 40.0 min and discharges 35,251 gal. A hydrant that gives 1,000 gpm is enough, with a ratio of 0.88.

Why it matters

The calculator helps water utility crews, contractors, inspectors and students to plan the flushing of a new main, to check if a hydrant gives enough flow for the velocity needed, and to estimate the time of the flushing and the volume of water to discharge or to haul.

Good to know

Open the hydrant or the blow-off slowly to avoid a pressure surge, and flush from the clean end toward the dirty end. Keep a hose or a pipe to carry the water to a safe place, and dechlorinate or filter the water when it is required. Continue until the water is clear, and then take the samples for the bacteriological tests.

The water main disinfection chlorine dose calculator gives the chlorine for the next step, the pipe test leakage allowance calculator checks the pressure test, the hydrostatic test pressure calculator gives the test pressure and the trench pipe laying production calculator plans the laying of the pipe.

Frequently asked questions

Why flush a water main?

A new or repaired water main is flushed before the disinfection and before it is put in service, to remove the dirt, the stones, the construction debris and the air that stay in the pipe. The flushing is done at a high velocity, so that the water can carry the particles to the outlet. A pipe that is not flushed can give a dirty or a bad water to the customers, and it can damage the meters.

What velocity is used?

The usual minimum velocity for the flushing is 2.5 ft/s, or 0.75 m/s, in the pipe, and a higher velocity, 3 to 5 ft/s, is better when the hydrant gives enough flow. The flow needed is the velocity times the section of the pipe. A large pipe needs a large flow, and the flow available at a hydrant often limits the diameter that can be flushed with this method.

How many volume changes are made?

The flushing is made until the water is clear, and a usual minimum is to change the volume of the pipe at least three times. The time is the number of changes times the length of the pipe divided by the velocity. The total volume of water is the flow times the time, which is also the volume of the pipe times the number of changes. This water must be discharged where it does not cause erosion or damage.

What are the limits of the calculator?

The calculator gives the flow, the time and the volume for a pipe with a constant diameter. It does not include the dechlorination of the water that is discharged, the control of the erosion at the outlet, the pressure loss in the system, the effect of the valves, the branches, the air release or the sampling. The flushing must follow the standard of the water utility and the permit for the discharge.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.