The timber char depth calculator gives the char depth and the remaining section of a wood beam or column after a fire of a given duration, from the NDS method, with the section modulus and area that remain.
How the calculation works
- Enter the width and the depth of the timber beam or column.
- Choose the required fire resistance (30 minutes to 2 hours) and the number of exposed sides.
- The calculator finds the char depth a = 1.5 t^0.813 from the NDS and the effective char depth 1.2 a, which includes the heated layer with no strength.
- It gives the remaining section, the section modulus and the area retained after the fire exposure.
Example
A glulam beam of 6.75 in × 12 in is exposed on 3 sides for 1 hour. The char depth is 1.5 × 1^0.813 = 1.50 in, and the effective char depth is 1.2 × 1.5 = 1.80 in. The remaining section is 3.15 in wide (6.75 − 2 × 1.8) and 10.20 in deep (12 − 1.8). The section modulus retained is 3.15 × 10.2² / (6.75 × 12²) = 33.7% and the area retained is 39.7%.
Why it matters
The calculator helps structural engineers, architects, builders and students to check the fire resistance of heavy timber and glulam members, to choose a member size for a rating of 30 minutes to 2 hours and to compare it with steel and with protected solutions. It supports the first design of exposed timber structures.
Good to know
Add the effective char depth on all exposed faces, including the corners, which are rounded in a real fire. Check that the remaining section still carries the load of the fire design situation, and protect the connections and steel plates. Consider the rate of an engineered product such as cross-laminated timber, which can differ from solid wood. A fire engineer or the building official must approve the design.
Related tools
The wood beam span calculator sizes timber beams, the beam deflection calculator covers deflection, the steel column capacity calculator covers steel and the Euler buckling calculator covers column buckling.