Total dynamic head (TDH) calculator: pump head, friction loss and shaft power

Enter the flow, the pipe size and length, the lift and the discharge pressure to get the total dynamic head of a pump, the friction loss, the velocity and the shaft power.

Updated on
Your inputs
gpm

Value out of range

in

Value out of range

ft

Value out of range

ft

Value out of range

Value out of range

ft

Value out of range

psi

Value out of range

%

Value out of range

Results

Total dynamic head

126.3 ft

Friction head loss in the pipe
34.43 ft
Flow velocity
6.81 ft/s
Normal velocity
Velocity head
0.72 ft
Pressure head at the discharge
46.2 ft
Shaft power required
7.36 hp
Shaft power required in kilowatts
5.49 kW

The total dynamic head (TDH) is the height of liquid a pump has to deliver at a given flow. The total dynamic head calculator adds the static lift, the friction loss of the pipe, the pressure required at the discharge and the velocity head, and then gives the shaft power needed.

How the calculation works

  • Enter the flow rate, the inside diameter of the pipe, its straight length and the equivalent length of the fittings and valves.
  • Enter the Hazen-Williams C of the pipe (about 100 for old steel, 120 for new steel, 140 for plastic and 150 for new PVC).
  • Enter the static lift between the water level at the suction and the discharge point, and the pressure needed at the discharge.
  • The calculator adds the static head, the friction head, the pressure head and the velocity head to give the total dynamic head, then the shaft power for the pump efficiency.

Example

A pump moves 150 gpm through 400 ft of 3 in pipe, with 60 ft of equivalent length for the fittings and a C of 120. The friction head is 34.4 ft and the velocity is 6.81 ft/s, which gives a velocity head of 0.72 ft. The static lift is 45 ft and the discharge needs 20 psi, which is 46.2 ft. The total dynamic head is 45 + 34.4 + 46.2 + 0.72 = 126.3 ft. At an efficiency of 65 %, the shaft power is 7.36 hp, or 5.49 kW.

Why it matters

The calculator helps plumbers, irrigation designers, engineers and homeowners to size a pump for a well, a booster, a pond, a fountain, a sprinkler system or a water transfer. It shows how much of the pump energy goes to the lift, to the friction and to the pressure, and where the pipe size can be improved.

Good to know

The calculator is for water at ordinary temperatures in full pipes of constant diameter, with the Hazen-Williams equation. It does not use the suction side details such as the NPSH, a variable diameter, the pump curve, the viscosity of other liquids or the elevation change of long pipelines. Add a margin for the ageing of the pipe and the wear of the pump, and check the pump curve of the manufacturer.

The pump power calculator gives the energy needed for a given head and flow, the pipe flow velocity calculator checks the speed in the pipe, the friction loss calculator covers the pipe losses with other equations, and the NPSH calculator checks that the pump does not cavitate.

Frequently asked questions

What is the total dynamic head?

The total dynamic head (TDH) is the total energy per unit weight that a pump must give to the fluid, expressed as a height of liquid. It is the sum of the static head (the height between the suction and the discharge levels), the friction head lost in the pipes and fittings, the pressure head required at the discharge and the velocity head. A pump is chosen so that its curve crosses the system curve at the required flow and TDH.

How is the friction loss computed here?

The friction loss uses the Hazen-Williams equation, which is common for water in full pipes at ordinary temperatures. The loss depends on the flow to the power 1.852 and on the diameter to the power 4.87, so a small increase in the pipe diameter lowers the loss a lot. The fittings and valves are included as an equivalent length of straight pipe, taken from tables.

What is the difference between TDH and static head?

The static head is only the lift between the two levels, and it does not depend on the flow. The TDH adds the losses and the pressure needed at the discharge, and it grows with the flow. For a long, narrow pipe the friction can be larger than the static head. This is why a pump must be chosen from its curve at the real flow and not from the lift alone.

What C value should I use?

The Hazen-Williams coefficient C describes the roughness of the inside of the pipe. Typical values are 150 for new PVC and plastic, 140 for new steel or copper, 130 for new cast iron, 120 for older steel and 100 for old cast iron. The value falls with age and corrosion. For design, use a conservative value, since a lower C gives a higher friction loss and a larger pump.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.