Wood column capacity calculator: axial load of a wood post with buckling (NDS)

Enter the column size, the unbraced length, the end conditions, the compression stress and the modulus to get the slenderness, the critical buckling stress, the stability factor Cp and the allowable axial load.

Updated on
Your inputs
in

Value out of range

in

Value out of range

ft

Value out of range

psi

Value out of range

psi

Value out of range

Results

Allowable axial load

20,918 lb

Slenderness ratio le/d
21.8
The slenderness is within the limit of 50
Critical buckling stress FcE
1,002 psi
Column stability factor Cp
0.692
Allowable compression stress Fc′
692 psi

The wood column capacity calculator gives the allowable axial load of a sawn lumber column or post from its size, unbraced length, end conditions and the reference stresses, with the column stability factor Cp of the NDS.

How the calculation works

  • Enter the actual width and depth of the column (a nominal 6 × 6 is 5.5 × 5.5 in) and the unbraced length.
  • Choose the effective length factor Ke from the end conditions, and the load duration factor.
  • Enter the reference compression stress Fc and the modulus of elasticity Emin of the species and grade, from the NDS supplement.
  • The calculator finds the slenderness le/d, the critical buckling stress FcE = 0.822 Emin / (le/d)², the stability factor Cp and the allowable load.

Example

A 6 × 6 post (5.5 × 5.5 in) is 10 ft long and pinned at both ends (Ke = 1.0), with Fc = 1,000 psi and Emin = 580,000 psi. The slenderness is 120 / 5.5 = 21.8, and FcE = 0.822 × 580,000 / 21.8² = 1,002 psi. With c = 0.8 for sawn lumber, Cp = 0.692, so Fc′ = 692 psi. The allowable load is 692 × 30.25 in² = 20,918 lb.

Why it matters

The calculator helps builders, engineers, architects and homeowners to check a wood post of a deck, a porch, a basement or a barn, to see the effect of the length and of the size on the load and to compare a 4 × 4 with a 6 × 6. It reproduces the NDS hand calculation for a column.

Good to know

Use the actual dimensions and not the nominal ones, and the reference values for the species and the grade you buy. Use the largest unbraced length for the weak axis, and the adjustment factors of the NDS. A post that carries a girder should have a good connection and bearing, and the footing must be checked too. For a house or a public use, follow the local code and consult an engineer.

The Euler buckling calculator covers the elastic buckling of columns, the steel column capacity calculator covers steel, the wood beam span calculator covers beams and the fence post depth calculator covers embedded posts.

Frequently asked questions

What is the column stability factor?

The column stability factor Cp of the National Design Specification for Wood Construction (NDS) reduces the allowable compression stress of a column to account for buckling. A short column fails by crushing and has Cp close to 1, while a slender column fails by buckling at a lower stress. The factor goes from 0 to 1 and uses the Ylinen equation, which blends the two failure modes in a smooth way.

How is the slenderness calculated?

The slenderness ratio is the effective length le = Ke × L divided by the smaller dimension d of the section, since the column buckles about the weak axis. The NDS limits le/d to 50 for solid columns. Ke depends on the end conditions: 1.0 for pinned ends, 0.8 for one end fixed and one pinned, 0.65 for both ends fixed, and 2.1 for a cantilever column. The recommended design values include the partial fixity found in practice.

What are the Fc and Emin values?

Fc and Emin are the reference values of the species and the grade, from the NDS supplement for sawn lumber or from the glulam data of the manufacturer. For Douglas fir-larch No. 1, posts and timbers, Fc is about 1,000 psi and Emin about 580,000 psi, but your values must come from the table for your lumber. The adjustment factors for the size, the moisture, the temperature and the load duration modify the reference stress.

What does the calculator not include?

It does not include combined bending and axial load, the bearing at the ends, the connections or the fire resistance. The column must also be checked for the compression perpendicular to the grain where it bears on the beam and on the footing. The factors of size and moisture are assumed to be already included in the Fc given. For a real structure, the design needs to be verified by an engineer.