Chilled water plant efficiency calculator: cooling capacity from the flow and delta T, and the kW per ton of the plant

Enter the chilled water flow, the supply and return temperatures and the power of the chiller, the pumps and the tower fans to get the capacity in tons, the chiller and plant kW per ton, the plant COP and the temperature difference.

Updated on
Your inputs
gpm

Value out of range

°F

Value out of range

°F

Value out of range

kW

Value out of range

kW

Value out of range

kW

Value out of range

kW

Value out of range

Results

Plant efficiency (chiller, pumps and tower)

0.66 kW/ton

Cooling capacity
300 tons
Chiller efficiency
0.55 kW/ton
Plant coefficient of performance
5.33
Chilled water temperature difference
12.0 °F
The temperature difference is good: the pumping energy stays low

The chilled water plant efficiency calculator gives the cooling capacity in tons of a chilled water loop from its flow and its temperature difference, with the kW per ton of the chiller and of the whole plant, including the pumps and the cooling tower, and the coefficient of performance.

How the calculation works

  • Enter the chilled water flow and the supply and return temperatures of the loop.
  • Enter the electric power of the chiller, of the chilled water pumps, of the condenser water pumps and of the cooling tower fans, measured or from the nameplates.
  • The calculator finds the cooling capacity in tons, the efficiency of the chiller alone and of the whole plant in kW per ton, the coefficient of performance and the temperature difference of the loop.

Example

A chilled water loop of 600 gpm is supplied at 44 °F and returns at 56 °F, so the difference is 12 °F. The capacity is 600 × 12 / 24 = 300 tons. The chiller uses 165 kW, or 0.55 kW/ton. With 11 kW of chilled water pumps, 14 kW of condenser pumps and 8 kW of tower fans, the plant uses 198 kW, or 0.66 kW/ton, which is a coefficient of performance of 3.517 / 0.66 = 5.33.

Why it matters

The calculator helps facility managers, mechanical engineers, energy auditors, commissioning agents and students to check the performance of a chilled water plant from simple measurements, to compare it with the targets and to find the effect of the auxiliaries. A plant efficiency far from the nameplate value often shows a problem such as a low delta T or a fouled condenser.

Good to know

Measure the flow and the temperatures at the same time as the power, in steady conditions, and use calibrated sensors. Compare the result at the same load with the design value. A temperature difference lower than design usually means that valves of the air handlers let too much flow, and a high kW per ton at a low load is normal for a single chiller. Record the values to follow the trend.

The cooling tower performance calculator covers the tower, the coefficient of performance calculator converts between efficiency units, the sensible heat ratio calculator splits the cooling load and the pump power calculator gives the power of the pumps.

Frequently asked questions

How is the capacity of a chilled water plant found?

The cooling capacity is the heat taken from the building by the chilled water. In US units it is 500 × gpm × ΔT in Btu/h, since 1 gpm of water carries 500 Btu/h per °F, and a ton of refrigeration is 12,000 Btu/h, so the capacity in tons is gpm × ΔT / 24. A flow of 600 gpm with a difference of 12 °F gives 300 tons. In SI units the capacity is the mass flow multiplied by 4.186 kJ/kg·K and by the difference of temperature.

What is the kW per ton?

The kW per ton is the electric power divided by the cooling capacity in tons, and it is the usual way to express the efficiency of a chiller in the United States. A lower value is better: a good water-cooled chiller is at 0.5 to 0.6 kW/ton, and an efficient plant, with the pumps and the tower, is at 0.6 to 0.8 kW/ton. The conversion to the coefficient of performance is COP = 3.517 / (kW per ton).

Why does the plant efficiency matter more than the chiller efficiency?

The chiller is only a part of the power of the plant. The pumps and the fans of the tower can be 20 to 30% of the total, and a plant with a very efficient chiller but with oversized pumps or a low temperature difference can use more energy than expected. For this reason the efficiency of the whole plant, which includes all the auxiliaries, is the number to follow, for example with a permanent metering.

What are the limits of the calculator?

The calculator gives an instant value from the measured flow, temperatures and power. The efficiency of a chiller varies a lot with the load, the temperature of the condenser water and the lift, and the annual efficiency is better expressed by an integrated part load value. A low temperature difference, a bypass flow or a poor calibration of the sensors will give a wrong capacity. The result is an indicator for an engineer or an energy auditor.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.